User Guide
F-24789-7 © Copyright 2008 TAC All Rights Reserved. 11
5. Install the cover plate with two screws. The cover plate and two screws are supplied
with the actuator.
6. If flexible conduit is to be installed on both sides of the actuator, repeat the preceding
steps to install the second conduit.
Auxiliary Switch Leads
The low voltage (24 Vac) auxiliary switch leads may be connected to a Class 2 circuit.
The line voltage (120 Vac and 240 Vac) auxiliary switch leads must be connected to a
Class 1 circuit and routed separately from any Class 2 circuit wiring. Refer to Figure-4.
Ribs
Cover Plate
Base
or
Figure-8 Flexible Conduit Installation to Either Side of Actuator.
Transformer
(AM-610 shown)
4 x 4
Conduit
Box
Cover Plate
Leave Knockout in place
Typical for 24 Vac
models (MP-52X3)
Line voltage motor or auxiliary switch
leads only when connected to other
than Class 2 circuits.
Low voltage motor or control leads
may be connected to a Class 2
circuit if routed separately from
line voltage circuit wiring.
Note: Class 2 circuit wiring must be routed
separately from the wiring from other circuits.
Do not route Class 2 circuit wiring in the same
conduit box with the line voltage transformer.
Figure-9 MP-5200 Series Wiring with Separation for Line Voltage and Class 2 Circuits.