Product Overview
20 © Copyright 2011 Schneider Electric All Rights Reserved. F-15479-11
Typical Actuators which require CP-8301-024 purchased separately: MP-361, 
MP-371, MP-381, MP-382, MP-2113-500.
Figure-17 External Wiring for CP-8301-024, Vdc Interface with 24 Vac Actuators.
4 5 6 7
3
8
2 H
1 GX
Green Wires
Case
Ground Screw
Yellow / Black
Blue  / B la ck
Red / Black
Brown
Brown / White
Brown /  Black
Black / Blue
Black
To  24  Vac
Power Su pply
1
The  Blue  wire  on  th e CP- 83 01 -024  is grou nd ed.  To u ng ro un d t he  Blue  wire,  remove the  Gree n jump er 
wir e  be twee n te rminal X a nd  th e case gr oun d  screw.
The actuator rotates  clockwise on an increasing Vdc input signal  between Blue (-, Common) and 
Yellow (+). To  r ota te  the  act ua tor count erclockwise o n a n in cre ase  in in put  sign al, reverse  th e 
Blue/Black and  Red/Black leads and reverse the Brown/Black and Brown/White leads.
When ever  it  is no t con ne cted , ta pe  off  the  red  powe r supply lead  fr om  th e CP -8 30 1-02 4 a ctua tor d rive .
Con ne ct Gree n/Yellow g roun d  wir e f rom  CP  act ua tor d rive  to  case  grou nd  screw.
1
2
2
CP-8301-024
Solid  Stat e
Actu ator Drive
(V dc I np ut
Sign al with
3 Vdc Fixed
Span and
2 t o 1 2 V dc
Adjustable
Start P oint
Blue  (-,  Common)
Yellow (+,  In put  Sign al)
Red (+20  Vdc,
50 mA  Power Supply)
1
Red
Yellow
Blu e
+2 0
OP
CO M
Typical
Co ntr ollers
Yellow
Blue
AO
CO M
SH
Typi ca l DD C
Controllers
3
CP-8102
SLC-8xxx
TP-8xxx
To Controller
(Below)
Gre en / Yellow
4
3