F-15479-8 © Copyright 2007 TAC All Rights Reserved. 5
Table-4 MP-4xxx Series Model Chart.
Actuator
Part
Number
Internal
Wiring
(See
Figure)
Input Control Signal External Wiring (and required Interface Module that must be purchased separately)
(See Figure)
Power
Requirements
Output Shaft
Aux.
Switch
Built-in
Trans-
former
b
2-Position
SPST
Spring
Return
2-Position
or
Floating
SPDT
TAC Microtherm
a
(Proportional Electric)
135 to
1,000 Ω
Slidewire
Voltage Vdc
Current
mAdc
Volts Hz. Amps
Torque
Lb.-in.
(N-m)
Timing
Seconds
(No Load)
Degrees of
Rotation
Spring
Return
Standard
Sequencing
of Two
Actuators
5-Position
(Adj. Min
Position)
MP5-4651 Figure-26 Figure-4 Figure-6
Figure-15
(AE-504)
Figure-18
(CP-8301-240)
Figure-21
c
or
Figure-23
d
240 50 0.25 50 (5.6) 108 180 (Adj.
f
) CW SPDT Yes
MP-4701 Figure-31 Figure-13 240 60 0.25 50 (5.6) 90 180 (non-Adj.) CCW None Yes
MP5-4751 Figure-26 Figure-4 Figure-6
Figure-15
(AE-504)
Figure-18
(CP-8301-240)
Figure-21
c
or
Figure-23
d
240 50 0.25 50 (5.6) 108 180 (non-Adj.) CCW SPDT Yes
MP-4851 Figure-26 Figure-6
Figure-15
(AE-504)
Figure-18
(CP-8301-240)
Figure-21
c
or
Figure-23
d
240 60 0.25 220 (24.9) 130 180 (Adj.
f
) No SPDT Yes
MP5-4851 Figure-26 Figure-6
Figure-15
(AE-504)
Figure-18
(CP-8301-240)
Figure-21
c
or
Figure-23
d
240 50 0.25 220 (24.9) 156 180 (Adj.
f
) No SPDT Yes
a Typical TAC Microtherm Controllers: PP-22x Series; TP-1xx Series; TP-4xx Series; TP-101x Series; TP-103x Series; and TP-1xxxx Series.
b Units with a “-2” suffix, e.g. MP-xxxx-xxx-2-x, include a built-in transformer (used for TAC Microtherm or with AE-504) with secondary leads wired externally to terminals 7 and 8 of the actuator. Red (24 Vac) to terminal 8 and Blue
(12 Vac) to terminal 7. When these actuators are used with controllers other than TAC Microtherm or AE-504, disconnect the Red and Blue leads and tape off. Note: Models prior to “-2” suffix had transformer wired directly to
potentiometer. To disconnect the transformer, remove the back plate of the actuator, disconnect and tape the transformer leads.
c Requires CP-8391-910.
d Requires CP-8391-716.
e Units with a “-0-0-2” suffix are in compliance with CE requirements.
f Rotation adjustable 45 to 320°. Caution: On actuators with proportional input signals changing the rotation will affect the control, since the internal feedback potentiometer’s travel is fixed.
g MP-371 models with the “-621” suffix are obsolete.
h Integral solid state drive accepts 2-15 Vdc voltage.
i MP-495 is not rated for UL or CSA