User Guide

Table Of Contents
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 3
Actuators in the actuator selection tables below with “-600” suffix have the CP-8301-120 factory installed. All CP-8301s have a fixed span of 3 Vdc
to drive the actuator full stroke and a start point adjustable from 2 to 12
Vdc (factory set 6 Vdc).
The CP-8391-91x series have a fixed range of 4 to 20 mAdc to drive the actuator full stroke. Refer to CP-8391-910 Series 4 to 20 mA Electronic
Actuator Drive General Instructions F-22453. The CP-8391-716 has an adjustable span of 4 to 16 mAdc (factory set for 16) and adjustable start
point of 2 to 16 mAdc (factory set for 4). The input signal on CP-8391-716 is optically isolated. Refer to CP-8391-716 Electronic Actuator Drive
General Instructions F-21220.
Table-1 MP-2xxx Series Model Chart.
Table-2 MP-3xx Series Model Chart.
Actuator
Part
Number
Internal
Wiring
(See
Figure)
Input Control Signal External Wiring (and required Interface Module that must be purchased separately)
(See Figure)
Power Requirements Output Shaft
Aux.
Switch
Built-in
Trans-
former
b
2-Position
SPST
Spring
Return
2-Position
or
Floating
SPDT
TAC Microtherm
a
(Proportional Electric)
135 to
1,000 Ω
Slidewire
Voltage Vdc Current mAdc Volts Hz. Amps
Torque
Lb.-in.
(N-m)
Timing
Seconds
(No Load)
Degrees of
Rotation
Spring
Return
Standard
Sequencing
of Two
Actuators
5-Position
(Adj. Min
Position)
MP-2113-500 Figure-27 Figure-5 Figure-7
Figure-14
(AE-504)
Figure-17
(CP-8301-024)
Figure-19
(CP-8391-913)
24 60 2.2 50 (5.6) 25 180 (nonAdj.) No SPDT
MP-2150-500 Figure-29 Figure-6
Figure-15
(AE-504)
Figure-18
(CP-8301-120)
Figure-21
c
or
Figure-23
d
120 60 0.5 50 (5.6) 25 180 (non-Adj.) No SPDT Yes
Actuator
Part
Number
Internal
Wiring
(See
Figure)
Input Control Signal External Wiring (and required Interface Module that must be purchased separately)
(See Figure)
Power
Requirements
Output Shaft
Aux.
Switch
Built-in
Trans-
former
b
2-Position
SPST
Spring
Return
2-Position
or
Floating
SPDT
TAC Microtherm
a
(Proportional Electric)
135 to
1,000 Ω
Slidewire
Voltage Vdc Current mAdc Volts Hz. Amps
Torque
Lb.-in.
(N-m)
Timing
Seconds
(No Load)
Degrees of
Rotation
Spring
Return
Standard
Sequencing
of Two
Actuators
5-Position
(Adj. Min
Position)
MP-361
e
Figure-24 Figure-3 Figure-5 Figure-7
Figure-14
(AE-504)
Figure-17
(CP-8301-024)
Figure-19
(CP-8391-913)
24 60 2.5 50 (5.6) 90 180 (Adj.
f
) CW SPDT
MP-367
e
Figure-32 Figure-11 24 60 2.5 50 (5.6) 90 180 (Adj.
f
) CW SPST
MP-371
e g
Figure-24 Figure-3 Figure-5 Figure-7
Figure-14
(AE-504)
Figure-17
(CP-8301-024)
Figure-19
(CP-8391-913)
24 60 2.5 50 (5.6) 90 180 (nonAdj.) CCW SPDT
MP-377
e
Figure-32 Figure-11 24 60 2.5 50 (5.6) 90 180 (nonAdj.) CCW SPST
MP-379
e
Figure-30 Figure-12 24 60 2.5 50 (5.6) 90 180 (nonAdj.) CCW None
MP-381
e
Figure-24 Figure-5
Figure-14
(AE-504)
Figure-17
(CP-8301-024)
Figure-19
(CP-8391-913)
24 60 2.2 220 (24.9) 130 180 (Adj.
f
) No SPDT
MP-382
e
Figure-24 Figure-5
Figure-14
(AE-504)
Figure-17
(CP-8301-024)
Figure-19
(CP-8391-913)
24 60 2.2 220 (24.9)
130 to
1300 (Adj.)
180 (Adj.
f
) No SPDT
MP-387
e
Figure-32 Figure-11 24 60 2.2 220 (24.9) 130 180 (Adj.
f
) No SPST
MP-389
e
Figure-30 Figure-12 24 60 2.2 220 (24.9) 130 180 (Adj.
f
) No None
a Typical TAC Microtherm Controllers: PP-22x Series; TP-1xx Series; TP-4xx Series; TP-101x Series; TP-103x Series; and TP-1xxxx Series.
b Units with a “-2” suffix, e.g. MP-xxxx-xxx-2-x, include a built-in transformer (used for TAC Microtherm or with AE-504) with secondary leads wired externally to terminals 7 and 8 of the actuator. Red (24 Vac) to terminal 8 and Blue
(12
Vac) to terminal 7. When these actuators are used with controllers other than TAC Microtherm or AE-504, disconnect the Red and Blue leads and tape off. Note: Models prior to “-2” suffix had transformer wired directly to
potentiometer. To disconnect the transformer, remove the back plate of the actuator, disconnect and tape the transformer leads.
c Requires CP-8391-910.
d Requires CP-8391-716.
e Units with a “-0-0-2” suffix are in compliance with CE requirements.
f Rotation adjustable 45 to 320°. Caution: On actuators with proportional input signals changing the rotation will affect the control, since the internal feedback potentiometer’s travel is fixed.
g MP-371 models with the “-621” suffix are obsolete.