20 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators which require CP-8301-024 purchased separately: MP-361,
MP-371, MP-381, MP-382, MP-2113-500.
Figure-17 External Wiring for CP-8301-024, Vdc Interface with 24 Vac Actuators.
4 5
6 7
3
8
2
H
1
G
X
Green Wires
Case
Ground Screw
Yellow / Black
Blue / Black
Red / Black
Brown
Brown / White
Brown / Black
Black / Blue
Black
To 24 Vac
Power Supply
1
1 The Blue wire on the CP-8301-024 is grounded. To unground the Blue wire, remove the Green jumper
wire between terminal X and the case ground screw.
2 The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common) and
Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse the
Blue/Black and Red/Black leads and reverse the Brown/Black and Brown/White leads.
3 Whenever it is not connected, tape off the red power supply lead from the CP-8301-024 actuator drive.
2
CP-8301-024
Solid State
Actuator Drive
(Vdc Input
Signal with
3 Vdc Fixed
Span and
2 to 12 Vdc
Adjustable
Start Point
Blue (-, Common)
Yellow (+, Input Signal)
Red (+20 Vdc,
50 mA Power Supply)
1
Red
Yellow
Blue
+20
OP
COM
Typical
Controllers
Yellow
Blue
AO
COM
SH
Typical DDC
Controllers
3
CP-8102
SLC-8xxx
TP-8xxx
To Controller
(Below)