User Guide

Table Of Contents
2 © Copyright 2007 TAC All Rights Reserved. F-15479-8
SPECIFICATIONS
Actuator Inputs
Input Control Signals: Refer to the actuator selection tables beginning on page 3 for input
control signal capability versus specific actuator models.
Floating, Requires one Single Pole Double Throw (SPDT) switch with floating (center
off) position rated at 0.9 amps @ 24 Vac or two Single Pole Single Throw (SPST)
switches rated at 0.9 amps @ 24 Vac.
Two-Position,
SPDT Requires snap acting switch rated at 0.9 amps @ 24 Vac.
SPST Can be used with certain spring return actuators. Switch must be rated to
handle actuator power requirements.
TAC Microtherm
®
, Proportional Electrical system with the following typical controllers:
PP-22x series, TP-1xx series, TP-2xx series, TP-3xx series, TP-4xx series, TP-1xxx
series, and TP-1xxxx series.
Standard Control of a single actuator.
Sequencing Control of two actuators in sequence.
Five-Position Used typically for adjustable minimum position (five positions) of an
economizer actuator.
Slidewire and Paralleling, Requires AE-504 paralleling relay. Refer to AE-504 Solid
State Paralleling Relay General Instructions F-16524. AE-504 accepts 100 Ω to
1000
Ω slidewires.
Voltage Vdc, Requires CP-8301-xxx series of solid state actuator drives. Refer to
CP-8301 Solid State Actuator Drive General Instructions F-14940. Refer to the
actuator selection tables beginning on page 3.
Current mAdc, Requires CP-8391-xxx series of solid state actuator drives. Refer to the
actuator selection tables beginning on page 3.
Power Requirements: Refer to the actuator selection tables beginning on page 3 to
determine power requirements.
Connections:
MP-3xx, 4xx, 2xxx, 4xxx, Coded screw terminals.
Models with “-600” Suffix, Coded screw terminals except for input signal which are
color coded pigtails.
Actuator Outputs
Torque: Refer to the actuator selection tables beginning on page 3 to determine the
actuator torque rating.
Nominal Damper Area: Actuator selection should be made in accordance with the damper
manufacturer’s specifications.
Stroke (Degrees of Rotation), Refer to the actuator selection tables beginning on page
3 for information on degrees of rotation.
Auxiliary Switch, Refer to the actuator selection tables beginning on page 3 for the
models that include an auxiliary switch. Refer to Table-6 for ratings.
Spring Return: Refer to the actuator selection tables beginning on page 3 for models that
are spring return.
Environment
Ambient Temperature Limits:
Shipping and Storage, -40 to 160 °F (-40 to 71 °C).
Operating, -40 to 136 °F (-40 to 58 °C).
Humidity: 5 to 95% RH, non-condensing.
Locations: NEMA 1
NEMA 4 for non-spring return actuators with AM-363.
Agency Listings:
UL 873, Underwriters Laboratories (File #E9429 Category Temperature Indicating and
Regulating Equipment).
CSA, Canadian Standards Association (File #LR3728).
European Community, EMC Directives (89/336/EEC and 92/31/EEC). Low Voltage
Directive (72/23/EEC). Refer to
Table-2 and Table-3 to identify specific models that are in
compliance with CE requirements.
Hazardous Location Models, UL file #29291. Designed for use in hazardous locations
N.E.C., Class 1, Groups C and D, and Class 2, Groups E, F, and G.
Temperature code
T6 for hazardous housing.