Typical Actuators: MP-465, MP-475, MP-485, MP-486, MP-495, MP-2130-500,
MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.
Typical TAC Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx
Series, TP-4xx Series, and TP-101x Series.
Standard Wiring:
C=Common of Switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).
B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).
Typical Cooling TAC Microtherm: TP-1031.
C =Common of switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature rise and drives the actuator CCW (opens valve).
B =Closes on temperature drop and drives the actuator CW (closes valve).
Figure-9 External Wiring of TAC Microtherm Controller with Line Voltage
Actuator – Standard Wiring.
Typical Actuators: MP-465, MP-475, MP-485, MP-486, MP-495, MP-2130-500,
MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.
Typical TAC Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx
Series, TP-4xx Series, and TP-101x Series.
Reversed Wiring:
C =Common of switch to R and B.
1 =Feedback from actuator (12 Vac with actuator full CCW to 24 Vac at CW end).
R =Closes on temperature (pressure) drop and drives the actuator CW (closes valve).
B =Closes on temperature (pressure) rise and drives the actuator CCW (opens valve).
Figure-10 External Wiring of TAC Microtherm Controller with Line Voltage
Actuator – Reversed (Cooling) Wiring.