Typical Actuators which require CP-8301-120 purchased separately: MP-465,
MP-475, MP-483, MP-485, MP-486, MP495, MP-2130-500, MP-2150-500.
Typical Actuators which require CP-8301-240 purchased separately:
MP5-2151-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.
Figure-18 External Wiring for CP-8301-120 and CP-8301-240, Vdc Interface with Line Voltage
Actuators with Internal Transformer.
4
5
6 7
3
8
2
L1
1
L2X
Green Wire
Case
Ground Screw
Yellow / Black
Blue / Black
Red / Black
Brown
Brown / White
Brown / Black
Black
To AC
Power Supply
White (CP-8301-120, 120 Vac)
White / Black (CP-8301-240, 240 Vac)
Tape
Red
Blue
1
1 The Blue wire on the CP-8301-120 and CP-8301-240 is grounded. To unground the Blue wire,
remove the Green jumper wire between terminal X and the case ground screw.
2 The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common)
and Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse
the Blue/Black and Red/Black leads, and reverse the Brown/Black and Brown/White leads.
3 Remove Red and Blue actuator transformer leads from actuator terminals 7 and 8 and tape the
leads off. On older actuators, remove back cover of actuator and cut and tape the leads from
the transformer to the feedback transformer.
4 Whenever it is not connected, tape off the red power supply lead from the CP-8301-120 or
CP-8301-240 actuator drive.
2
Blue (-, Common)
Yellow (+, Input Signal)
Red (+20 Vdc,
50 mA Power Supply)
1
CP-8301-120
(120 Vac)
CP-8301-240
(240 Vac)
Solid State
Actuator Drive
(Vdc Input Signal
with 3 Vdc Fixed
Span and
2 to 12 Vdc
Adjustable Start
Point
3
Red
Yellow
Blue
+20
OP
COM
Typical
Controllers
Yellow
Blue
AO
COM
SH
Typical DDC
Controllers
4
CP-8102
SLC-8xxx
TP-8xxx
To Controller
(Below)