Product Overview

F-15479-11 © Copyright 2011 Schneider Electric All Rights Reserved. 27
Typical Actuators: MP-2130-500, MP-2150-500, MP5-2151-500.
Figure-29 Internal Wiring for Line Voltage Actuators without Limit Switches and Built-in Transformer
(Actuator is Stall Type with Built-in Mechanical Stops).
Typical Actuators: MP-379 and MP-389
.
Figure-30 Internal Wiring for 24 Vac Five-Position Actuators.
L1
8
7
6
5
4
3
2
1
X
L2
M
o
t
o
r
CW CCW
CWCCW
Shading
Coils
100
Ω
Internal
Potentiometer
CCW
CW
Auxiliary
Switch
Case
Screw
Green
Wire
Internal
Transformer
0 Vac
Blue
12 Vac
24 Vac
Red
Field
Coil
Green Case
Ground Screw
2
1
1 Used for field grounding.
2 External green jumper from terminal X to case ground is only
available on current MP-xxx-xxx-x-2 models.
3 On models prior to current MP-xxx-xxx-2-x the Red and Blue
transformer leads were wired directly to potentiometer.
3
3
H
8
7
6
5
4
3
2
1
X
G
M
o
t
o
r
CW CCW
CWCCW
Shading
Coils
100
Ω
Internal
Potentiometer
CCW
CW
Case
Screw
Green
Wire
Field
Coil
Limit Switches
Green Case
Ground Screw
Case Screw
Green
Wire
1
1 Used for field grounding.
2 External green jumpers from
terminals X and G to case ground is
only available on current
MP-xxx-xxx-x-2 models.
2
2