Product Overview

F-15479-11 © Copyright 2011 Schneider Electric All Rights Reserved. 21
Typical Actuators which require CP-8301-120 purchased separately: MP-465,
MP-475, MP-483, MP-485, MP-486, MP495, MP-2130-500, MP-2150-500.
Typical Actuators which require CP-8301-240 purchased separately:
MP5-2151-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.
Figure-18 External Wiring for CP-8301-120 and CP-8301-240, Vdc Interface with Line Voltage
Actuators with Internal Transformer.
4 5 6 7
3 8
2 L1
1
L2X
Green Wire
Case
Ground Screw
Yellow / Black
Blue / B la ck
Red / Black
Brown
Brown / White
Brown / Black
Black
To AC
Power Supply
White (CP-83 01 -120 , 1 20 Vac)
White / Black (CP-8 301 -240 , 2 40 Vac)
Tap e
Red
Blue
1
3
The Blu e wire on th e CP -8 30 1-12 0 a nd CP-830 1-24 0 is grou nde d. To ung roun d t he Blue wire,
remove the Green jumper wire between terminal X and the case ground scree.
The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common)
an d Ye llow (+). To rotat e th e actu ato r cou nte rclo ckwise on an increa se in inp ut sig na l, re verse
th e B lu e/ Black a nd Red /Black lead s, an d reverse t he Brown/ Black a nd Brown /White lead s.
Remove Red a nd Blue actu at or tr ansf ormer lead s from actu at or ter minals 7 and 8 a nd tap e th e
leads off. On older actuators, remove back cover of actuator and cut and t ape the leads from
the transformer to the feedback transformer.
When ever it is no t conne cte d, t ap e o ff th e re d p ower su pp ly lead fr om th e CP -830 1-120 or
CP-83 01 -240 actu at or drive.
Connect Green/Yellow ground wire from CP actuator drive to case ground screw.
2
Blue (-, Common)
Yellow (+, Input Signal)
Re d (+20 Vd c,
50 mA Po wer Su pp ly)
1
CP-8301-120
(120 Vac)
CP-8301-240
(240 Vac)
Solid Sta te
Actuator Drive
(Vdc Input Signal
with 3 Vdc Fixed
Span and
2 to 1 2 Vdc
Adjustable Start
Point
3
Ye l l o w
Blue
AO
COM
SH
Typical DDC
Co nt ro ll e rs
4
To Controller
(Below)
5
4
2
1
Green / Yello w