Product Overview
F-15479-11 © Copyright 2011 Schneider Electric All Rights Reserved. 19
Typical Actuators which require CP-8301-120 purchased separately: MP-421,
MP-422, MP-423, MP-424, MP-451, MP-452, MP-454.
Typical Actuators with CP-8301-120 factory installed and wired: MP-461-600,
MP-471-600, MP-481-600, MP-2110-601.
Note: CP-8301-120 is marked CP-8301-620 on factory assemblies.
Figure-16 External Wiring for CP-8301-120, Vdc Interface with Line Voltage
Actuators without Internal Transformer.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
Case
Ground Screw
CP-8301-120
Solid State
Actuator Drive
(V dc In pu t
Signal with
3 Vdc Fixed
Span and
2 to 1 2 V dc
Adjustable
Sta rt Point
Blue (-, Common)
Ye llo w (+, Input Signal)
Red (+20 Vdc,
50 mA P ower S upp ly)
Yellow / Black
Blue / B la ck
Red / Black
Brown
Brown / White
Brown / Black
Black
White
To A C
Power Su pply
1
2
1
Red
Ye l l o w
Blue
+20
OP
COM
Typical
Controllers
Yellow
Blu e
AO
COM
SH
Typical DDC
Co nt ro ll e rs
3
CP-8102
SLC-8xxx
TP-8xxx
To C ont ro l le r
(Below)
Green / Yello w
1
The Blue wire on the CP-8301-120 is grounded. To unground the Blue wire, remove the Green jumper
wire between terminal x and the case ground screw.
2
The act ua tor r ota tes clo ckwise on a n incr e asing Vd c inp ut sig na l bet we en Blu e (-, Common) a nd
Yellow (+). To rotate the act uator count erclockwise on an increase in input signal, reverse th e
Blue/Black and Red/Black leads and reverse the Brown/Black and Brown/White leads.
Whenever it is not connected, tape off the red power supply lead from the CP-8301-120 actuator drive.
Connect Green/Yellow wire from CP actuator drive to case ground screw.
3
4