Product Overview

F-15479-11 © Copyright 2011 Schneider Electric All Rights Reserved. 13
Typical Actuators: MP-361, MP-371, MP-381, MP-382, and MP-2113-500.
Typical Barber-Colman Microtherm Controllers: PP-22x Series, TP-2xx
Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.
C =Common of Switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full Counterclockwise rotation (CCW) to
12 Vac at Clockwise rotation (CW) end).
R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).
B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).
Typical Cooling Barber-Colman Microtherm: TP-1031.
C =Common of switch to R and B.
1 =Feedback from Actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature rise and drives the actuator CCW (opens valve).
B =Closes on temperature drop and drives the actuator CW (closes valve).
Figure-7 Barber-Colman Microtherm Controller with 24 Vac Actuators – Standard Wiring Diagram.
Typical Barber-Colman Microtherm Controllers: PP-22x Series, TP-2xx
Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.
C =Common of Switch to R and B.
1 =Feedback from Actuator (12 Vac with Actuator full CCW to 24 Vac at CW end).
R =Closes on temperature (pressure) drop and drives the actuator CW (closes valve).
B =Closes on temperature (pressure) rise and drives the actuator CCW (opens valve).
Figure-8 Barber-Colman Microtherm Controller with 24 Vac Actuators – Reversed (Cooling) Wiring
Diagram.
4 5
6 7
3
8
2
H
1
G
X
Green Wires
To 24 Vac
Power Supply
Case
Ground Screw
C
2
R
1
B
Case
Ground
Screw
Add
Jumper
Add Resistor
(Supplied With Actuator)
100
4 5
6 7
3
8
2
H
1
G
X
Green Wires
To 24 Vac
Power Supply
Case
Ground Screw
C
2
R
1
B
Case
Ground
Screw
Add
Jumper
Add Resistor
(Supplied With Actuator)