Submittal Sheet

Specifications
Power supply
Operating voltage (G–Y1 or G-Y2) 24 Vac +20%, -15%
Frequency 50/60 Hz
Power consumption 2.3 VA
Equipment rating
Rating Class 2 according to UL/cUL
Class III per EN60730
Auxiliary features
Feedback potentiometer 0 to 1000 Ω
(MF41-6043-510 and MF41-6083-510) <10 mA
Dual auxiliary switch contact rating
AC rating 24 Vac
4A resistive, 2A inductive
DC rating 12 to 30 Vdc
DC 2A
Switch Range
Switch A 0° to 90° with 5° intervals
Recommended range usage 0° to 45°
Factory setting
Switch B 0° to 90° with 5° intervals
Recommended range usage 45° to 90°
Factory setting 85°
Switching hysteresis
Function
Torque
MF41-6043 Series 35 lb-in (4 Nm)
MF41-6083 Series 70 lb-in (8 Nm)
Runtime for 90° opening or closing
MF41-6043 Series 90 sec. at 60 Hz (108 sec. at 50 Hz)
MF41-6083 Series 125 sec. at 60 Hz (150 sec. at 50 Hz)
Nominal angle of rotation 90°
Maximum angular rotation 95°
Mounting
Shaft size: Minimum shaft length 3/4-inch (20 mm)
EA1010R1
9/16 inch
15 mm
3/8 to 5/8 inch
8 -16 mm
1/4 to 1/2 inch
6 - 12.7 mm
Figure 1. Acceptable Shaft Sizes.
Housing
Enclosure NEMA Type 2
IP54 according to EN60529
Material Durable plastic
Gear lubrication Silicone-free
Ambient conditions
Ambient temperature
Operation –25°F to 130°F (–32°C to 55°C)
Storage and transport –40°F to 158°F (–40°C to 70°C)
Voltage Requirements for 6083 Series
at High Temperatures Minimum voltage: 24 Vac +20%, -10%
90°F to 130°F (32°C to 55°C)
Ambient humidity (non-condensing) 95% rh
Agency certification
UL 873
cUL certified to Canadian
Standard C22.2 No. 24-93
conformity
Electromagnetic Compatibility (EMC) 89/336/EEC
Emissions standards EN 61000-6-3:2001
Immunity standards EN 61000-6-2:2001
Requirements for electric actuators EN 60730-2-14:2001