User Guide
Table Of Contents
- Application
- Features
- . Two position models controlled by SPST controller
- . Floating models controlled by SPDT floating controllers
- . Proportional models controlled by 0-3 Vdc, 6-9 Vdc, 0-10 Vdc, 0-20 mAdc, 2-10 Vdc, or 4-20 mAdc. Control function direct/reverse action is jumper selectable
- . 105 lb force (467 newton) with 1/2" (13 mm) nominal linear stroke
- . 24 Vac, 120 Vac, and 230 Vac models
- . Rugged polymer housings rated for up to NEMA 2/IP54
- . Overload protection throughout stroke
- . Automatically sets input span to match valve travel
- . Compact size to allow installation in limited space
- . Manual override to allow positioning of valve and preload
- . Spring return operation
- . Direct mount to valves without separate linkage
- . Polymer housing rated for plenum use
- . Five year warranty
- Applicable Literature
- SPECIFICATIONS
- TYPICAL TWO POSITION CONTROL (wiring diagrams)
- Figure-1 Typical Wiring Diagrams for Two Position Actuators
- TYPICAL FLOATING CONTROL (wiring diagrams)
- TYPICAL PROPORTIONAL CONTROL (wiring diagrams)
- INSTALLATION
- Figure-8 Wire Diagram Notes Guide
- Inspection
- Requirements
- Precautions
- Location
- Mounting
- Changing Control Function (proportional units only)
- Installation: Mx51-710x Series Actuator to 1/2" to 2" VB-7xxx Series Valve Bodies, 2-Way Stem-Up Closed and 3-Way Mixing or Diverting Applications
- A. Preload the valve to insure proper close-off according to the numbered steps in Figure-10 and the text below. (Remove power before proceeding.)
- 1. Locate the steel jam nut that came packaged with the actuator. (Do not re-use the brass jam nut present on an existing valve.)
- 2. Screw the nut onto the valve stem all the way as far as it will go (you may need to use a TOOL-20-1 or a 5/16” open-end wrench). At least 1/2” of the valve stem should extend above the nut.
- 3. Thread the stem extension onto the valve stem, making contact with the jam nut. Raise the valve stem to the full up position.
- 4. Orient the actuator mounting bracket on the valve and tighten the hex mounting nut securely against the bracket using TOOL-37.
- 5. Insert the crank provided in the actuator cover. Wind the crank two turns counterclockwise. Press in the turn crank 1/8 turn counterclockwise to lock in position.
- 6. Rotate the stem extension until the through holes in the stem extension and rack line up. Insert connecting pin to secure stem extension and tighten jam nut against stem extension using TOOL-20-1 or a 5I16” open end wrench.
- B. Apply power to the actuator and check the system operation for heating or cooling output in response to the control signal.
- Installation: Mx51-710x Series Actuator to 1/2" to 2" VB-7xxx Series Valve Bodies, 2-Way Stem-Up Open
- A. Preload the valve to insure proper close-off according to the numbered steps to 10 and the text below. (Remove power before proceeding.)
- 1. Locate the steel jam nut that came packaged with the actuator. (Do not re-use the brass jam nut present on an existing valve.)
- 2. Screw the nut onto the valve stem all the way as far as it will go (you may need to use a TOOL-20-1 or a 5/16” open-end wrench). At least 1/2” of the valve stem should extend above the nut.
- 3. Thread the stem extension onto the valve stem, making contact with the jam nut. Push the valve stem to the full down position.
- 4. Orient the actuator mounting bracket on the valve and tighten the hex mounting nut securely against the bracket using TOOL-37.
- 5. Insert the crank provided in the actuator cover. Wind the crank counterclockwise until the actuator fully extends, then unwind 2 turns and press in and turn crank 1/8 turn counterclockwise to lock in position.
- 6. Rotate the stem extension until the through holes in the stem extension and rack lineup. Insert connecting pin to secure stem extension and tighten jam nut against stem extension using TOOL-20-1 or a 5I16” open end wrench.
- B. Apply power to the actuator and check the system operation for heating or cooling output in response to the control signal.
- Valve Mounting
- 1. Following general piping practices is recommended.
- 2. Apply pipe sealant sparingly to all but the last two threads of a properly threaded, reamed, and cleaned pipe. Make sure the ...
- 3. Start the joint hand-threading the pipe into the valve. If the thread alignment feels normal, continue to turn the pipe by hand as far as it will go.
- 4. Use a pipe wrench to fully tighten the pipe to the valve.
- 5. Insulate only the valve body and associated piping, not the actuator.
- 6. In chilled or cold water systems where the environment is humid, use a drip pan under the valve to catch condensate.
- Figure-11 Acceptable Mounting Orientations for Non-Steam Applications
- Figure-12 Acceptable Mounting Orientation for Steam Applications
- 1. Following general piping practices is recommended.
- MANUAL OVERRIDE OPERATION
- Figure-13 Unacceptable Mounting Orientation
- 1. Disconnect power from the actuator. The actuator will fully retract.
- 2. Without pushing down on the crank, crank the manual override counterclockwise until the actuator extends to the desired position. Push in until the mechanism locks in position. (The manual override lock will release the next time power is applied.)
- 3. If you desire to reposition the actuator manually from a locked position, turn the crank 1/8 turn counterclockwise and pull out to release. Adjust position as desired.
- Wiring Requirements
- Table-2 Power Wiring
- CHECKOUT
- THEORY OF OPERATION
- MAINTENANCE
- FIELD REPAIR
8 © Copyright 2007 TAC All Rights Reserved. F-27169-5
harmful interference if not installed and used in accordance with the instructions. Even
when instructions are followed, there is no guarantee that interference will not occur in a
particular setting—Which can be determined by turning the equipment off and on—the user
is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment to an outlet on a circuit different from that to which the receiver
is connected.
• Consult the dealer or an experienced radio/television technician for help.
Canadian Department of Communications (DOC)
Note: This Class B digital apparatus meets all requirements of the Canadian Interference-
Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le
material broilleur du Canada.
European Standard EN 55022
Warning: This is a Class B digital (European Classification) product. In a domestic
environment this product may cause radio interference in which case the user may be
required to take adequate measures.
Location Caution: Avoid locations where excessive moisture, corrosive fumes, vibration, or
explosive vapors are present.
Mounting • Mount the linear actuator directly on the valve in locations that clear the maximum
dimensions of the actuator case (see Figure-12).
• Ensure that the valve body is installed correctly. The arrow must point in the direction
of flow. With three-way valves observe stem position (stem up or stem down) for proper
flow characteristics. See Table 3.
• It is preferable that the actuator is mounted above the valve body. This will minimize the
risk of damage to the actuator in the event of condensation or a valve leak. Refer to
Figure-10.
Changing Control Function (proportional units only)
These actuators are equipped with a jumper to control the function of the signal as received.
See Figure-9. Factory setting is for direct acting. Remove cover to change jumper setting.