Table-4 Power Wiring Data.
Figure-3 Wiring of Multiple MA-52xx Series Actuators to Single Power Source.
Auxiliary Switch Leads
The low voltage (24 Vac) auxiliary switch leads may be connected to a Class 2 circuit.
The line voltage (120 Vac and 240 Vac) auxiliary switch leads must be connected to a
Class 1 circuit and routed separately from any Class 2 circuit wiring. Refer to Figure-7.
Wiring Connections Wire Lead Connections (No Conduit)
Make connections as required. Refer to Figure-1 for a wiring diagram of a typical application.
Refer to Figure-4 for a view of the actuator.
Note:
The cover plate and screw supplied with the actuator are not required with this
method.
Actuator
Voltage
Vac
Actuator Model
Number
Power Lead
Colors
Wire Size
GA
Maximum Wire Run
ft. (m)
120
MA-5210
Black & White 14 3,500 (1,067)
MA-5210-500
240
MA-5211
Black & White/Black 14 6,000 (1,829)
MA-5211-500
24
MA-5213
Black & Black/Blue
14
12
300 (91.5)
480 (146.3)
MA-5213-500
120
MA-5330
Black & White 14 3,500 (1,067)
MA-5330-500
24
MA-5333
Black & Black/Blue
14
12
300 (91.5)
480 (146.3)
MA-5333-500
To Vac Power
To Additional MA-52XX
Series Actuators
Black
Green
Green
MA-52XX
MA-52XX
24 Vac Black/Blue
120 Vac White
240 Vac White/Black