Product Overview
4 Copyright 2008 TAC All Rights Reserved. F-15070-14
TYPICAL APPLICATIONS (wiring diagrams)
Figure-1 Typical Wiring for MA-5xxx Series Actuators.
INSTALLATION
Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
Requirements • Job wiring diagrams.
• Tools (not provided):
– Digital Volt-ohm Meter (DVM).
– Appropriate drill and drill bit for mounting screws.
– Appropriate screw drivers and wrenches.
– TOOL-12, Wrench for adjustment of auxiliary switch.
– TOOL-19, Spring compression tool for AV-600.
– TOOL-37, 1-5/8" (41 mm) open-ended wrench.
• Training: Installer must be a qualified, experienced technician.
Warning:
• Disconnect power supply before installation to prevent electrical shock and equipment
damage.
• Make all connections in accordance with the wiring diagram and in accordance with
national and local electrical codes.
Use copper conductors only.
Caution:
• Static charges produce voltages high enough to damage the electronic components.
Follow static electricity precautions when installing or servicing the device(s). Discharge
any static electricity you may have accumulated by using wrist straps, or by touching a
known, securely grounded object.
• Do not exceed the ratings of the device(s).
• Do not apply power to the unit unless the damper linkage and/or the valve assembly
have been installed.
• Avoid locations where excessive moisture, corrosive fumes, or vibration is present.
• Do not install insulation on any part of the actuator.
Black
Green
MA-5XXX Actuator
NOTE: Actuator extends when
contacts are closed and retracts
when contacts are open
Actuator Voltage
Vac
Color(s) of
L2 Lead
L1
24
120
240
Black/Blue
White
White/Black
L2
Red/White (C)
Thermostat
or Switch
Orange (N.C.)
Brown (N.O.)
Aux. Switch Leads
(-500 Actuators only)