SPECIFICATIONS
Actuator Inputs
Control Circuit: Two wire, SPST.
Power Input: Refer to Table-1 and Table-2.
Connections: Color-coded 4 ft. (1.2 m) leads.
Actuator Outputs
Electrical:
Auxiliary Switch (MA-5xxx-500), 10 Amps, 120/240 Vac adjustable SPDT, factory set
to close the N.O. contact at the retracted end of stroke.
Mechanical:
Stroke,
Damper Approximately 2" (51 mm) from fully retracted to fully extended (includes
AM-601 linkage).
Valve Approximately 9/16" (14.3 mm) from fully retracted to fully extended.
Nominal Damper Area, Actuator sizing should be done in accordance with damper
manufacturer’s specifications.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 140° F (-40 to 60° C).
Operating,
Damper 0 to 140° F (-18 to 60° C).
Valve Refer to Table-3.
Humidity: 5 to 95% RH, non-condensing.
Location: NEMA Type 1.
Agency Listings:
UL 873, Underwriters Laboratories (File # E9429 Category Temperature-Indicating and
Regulating Equipment).
CSA, Certified for use in Canada by Underwriters Laboratories. Canadian Standard
C22.2 No. 24-93.
European Community, EMC Directive (89/336/EEC). Low Voltage Directive
(72/23/EEC).
Table-1 Model Chart for Damper Actuators.
Part
Number
Actuator Power Input
Timing in Seconds
@ 72° F (22°
C)
Torque Rating
(Extend & Retract)
lb.-in. (N-m)
AC
Voltage
+10/
-15%
Hz VA Watts
To Extend
(No Load
Stroke)
Retract
on Power
Loss
MA-5330 120
50 60 18 14 60 15 20 (2.3)
MA-5333 24