Product Overview
12 Copyright 2008 TAC All Rights Reserved. F-15070-14
Valve
For valve assembly details refer to AV-600, Valve Linkage Kit General Instructions, 
F-26279 or AV-601, Linkage Extension Kit General Instructions, F-26280. Refer to 
Figure-21 for external dimensions of the valve actuator.
Adjustments Auxiliary Switch (MA-5xxx-500)
The switching point is adjustable over the entire actuator stroke and is pre-set at the factory 
to close the N.C. contacts at the retracted end of stroke. Turning the switch adjustment 
screw CW (using TOOL-12), adjusts the make (or break) point closer to the extended end 
of stroke. (Refer to Figure-15). 
Figure-15  Auxiliary Switch Actuation Point Adjustment and 
Position Indication for MA-5xxx-500 Series.
CHECKOUT
After the entire system has been installed and the actuator has been powered up, perform 
the following checks for proper system operation.
Caution:
Never power the actuator without a spring return linkage attached.
Positioning with 
Controller
If the sensed media is within the controller’s setpoint range, the actuator can be positioned 
by adjusting the controller setpoint up and down. Check for correct operation of the actuator 
(valve or damper) while the actuator is being stroked.
Go, No-Go Test 1. Apply power to the actuator. The actuator motor should run and the actuator shaft should 
extend.
2. Remove power from the actuator. The actuator motor should stop running and the 
actuator shaft should spring-return to the retracted position.
Position Indication and
Switch Action Cam
Auxiliary Switch
Adjustment Screw
MA-52XX-500
Series