Product Overview

12 Copyright 2008 TAC All Rights Reserved. F-15070-14
Valve
For valve assembly details refer to AV-600, Valve Linkage Kit General Instructions,
F-26279 or AV-601, Linkage Extension Kit General Instructions, F-26280. Refer to
Figure-21 for external dimensions of the valve actuator.
Adjustments Auxiliary Switch (MA-5xxx-500)
The switching point is adjustable over the entire actuator stroke and is pre-set at the factory
to close the N.C. contacts at the retracted end of stroke. Turning the switch adjustment
screw CW (using TOOL-12), adjusts the make (or break) point closer to the extended end
of stroke. (Refer to Figure-15).
Figure-15 Auxiliary Switch Actuation Point Adjustment and
Position Indication for MA-5xxx-500 Series.
CHECKOUT
After the entire system has been installed and the actuator has been powered up, perform
the following checks for proper system operation.
Caution:
Never power the actuator without a spring return linkage attached.
Positioning with
Controller
If the sensed media is within the controller’s setpoint range, the actuator can be positioned
by adjusting the controller setpoint up and down. Check for correct operation of the actuator
(valve or damper) while the actuator is being stroked.
Go, No-Go Test 1. Apply power to the actuator. The actuator motor should run and the actuator shaft should
extend.
2. Remove power from the actuator. The actuator motor should stop running and the
actuator shaft should spring-return to the retracted position.
Position Indication and
Switch Action Cam
Auxiliary Switch
Adjustment Screw
MA-52XX-500
Series