Product Overview
10 Copyright 2008 TAC All Rights Reserved. F-15070-14
Linkage Assembly Damper
Note:
Each actuator in the MA-5x3x series is provided with a factory-installed damper
linkage. No separately-ordered linkage is required.
Caution:
Do not twist or exert any force on the actuator housing during installation. Either
turn the base by hand or, if necessary, use a 1-5/8" (41 mm) open-ended wrench (TOOL-
37) on the flats provided on the actuator base, or on the valve body mounting nut. (Refer to
Figure-2.)
1. Determine the best mounting position for the actuator as follows:
a. Determine, from the system requirements, if the damper should spring-return to the
open position (refer to Figure-12) or closed position (refer to Figure-13) whenever
power is lost to the actuator. For example, an outside air damper actuator is typically
linked so as to retract (spring-return) to the damper’s fully closed position (safe
position).
Figure-12 Dampers Open When Actuator Retracts
(Spring-Returns Open on Power Loss).
Figure-13 Dampers Open When Actuator Extends
(Spring-Returns Closed on Power Loss).
b. Be sure to allow adequate working space around the actuator mounting location to
mount the actuator, link it to the damper, and wire it into the system (refer to
Figure-20).
c. If possible, select a mounting position such that, at mid-stroke, the actuator crank
arm and the damper crank arm on the drive shaft are each at a 90° angle to the
damper rod (Refer to Figure-14). This is the recommended mounting position. It
may be necessary to swivel the actuator linkage to arrive at this mounting location.
Spring returns open
on loss of power
Open
Close
ExtendRetract
Damper Shaft
Spring returns open
on loss of power
Open
Close
Extend Retract
Damper Shaft










