User Guide
Schneider Electric 1354 Cliffo rd Ave. Loves Park, IL 61111 1-888 - 44 4 -1311 w ww.schneider-electric.co m / buildings
F-27599-4 March 2011 co
© 2011 Schneider Electric. All rights reserved.
7
Globe Valve Actuators & Assemblies
Forta
Select Valve/Actuator Combination Having Su cient Close o for Application
Valve Body
a
Close-o Ratings, psi (kPa)
Two-Way Valves P Code Size M400A (VB) M800A (VB) M1500A (VB)
VB-7211-0-3-P
VB-7211-0-4-P
VB-7212-0-4-P
VB-7213-0-4-P
VB-7214-0-4-P
VB-7215-0-4-P
VB-7221-0-4-P
VB-7222-0-4-P
VB-7223-0-4-P
VB-7224-0-4-P
VB-7225-0-4-P
VB-7253-0-4-P
VB-7263-0-4-P
VB-7273-0-4-P
VB-7283-0-4-P
-01, -02, -03, -04 1/2”(15 mm) 250 (1712) 250 (1712) —
-05, -06 3/4” (20 mm) 198 (1356) 250 (1712) —
-07, -08 1” (25 mm) 92 (630) 207 (1418) —
-09 1-1/4” (32 mm) 56 (384) 130 (890) —
-10 1-1/2” (40 mm) 37 (253) 88 (603) 177 (1212)
-11 2” (40 mm) 19 (130) 48 (329) 98 (671)
VB-8213-0-5-P
b
VB-8223-0-5-P
b
-12, -13, -14, -15,
-16
2-1/2” to 6” Do not use Do not use 125 (856)
Three-Way Valves P Code Size M400A (VB) M800A (VB) M1500A
VB-7312-0-4-P
VB-7313-0-4-P
VB-7314-0-4-P
VB-7315-0-4-P
-02, -04 1/2”(15 mm) 250 (1712) 250 (1712) —
-06 3/4” (20 mm) 198 (1356) 250 (1712) —
-08 1” (25 mm) 92 (630) 207 (1418) —
-09 1-1/4” (32 mm) 56 (384) 130 (890) —
-10 1-1/2” (40 mm) 37 (253) 88 (603) —
-11 2” (40 mm) 19 (130) 48 (329) —
VB-7323-0-4-P -04, -06, -08, -09,
-10, -11
1/2” to 2” 250 (1712) Do not use
VB-8303-0-5-P
b
-12, -13, -14, -15,
-16
2-1/2” to 6” Do not use Do not use 35 (241)
VB-9313-0-5-P
b
-12 2-1/2” Do not use
29 (199)
61 (418)
-13 3” Do not use
19 (130)
42 (288)
-14 4” Do not use
10 (68)
22 (151)
-15 5” Do not use Do not use 14 (96)
-16 6” Do not use Do not use 9 (62)
a. Not all bodies are available for all port codes.
b. Requires U-Bolt mounting style.
ACTUATOR VALVE SELECTION FOR THE FORTA NONSPRING RETURN ACTUATORS