Selection Guide
6 © Copyright 2008 TAC. All rights reserved. F-27490-4
Table-5 Select Valve/Actuator Combination Having Sufficient Close-off for Application
Valve Body Close-off Ratings, psi (kPa)
Two-Way Valves P Code Size M400A- (VB) M800A- (VB) M1500A- (VB)
VB-7211-0-3-P
VB-7211-0-4-P
VB-7212-0-4-P
VB-7213-0-4-P
VB-7214-0-4-P
VB-7215-0-4-P
VB-7221-0-4-P
VB-7222-0-4-P
VB-7223-0-4-P
VB-7224-0-4-P
VB-7225-0-4-P
VB-7253-0-4-P
VB-7263-0-4-P
VB-7273-0-4-P
VB-7283-0-4-P
-01, -02, -03, -04 1/2” (15 mm) 250 (1712) 250 (1712) —
-05, -06 3/4” (20 mm) 198 (1356) 250 (1712) —
-07, -08 1” (25 mm) 92 (630) 207 1418) —
-09 1-1/4” (32 mm) 56 (384) 130 (890) —
-10 1-1/2” (40 mm) 37 (253) 88 (603) 177 (1212)
a
-11 2” (50 mm) 19 (130) 48 (329) 98 (671)
a
Three-Way Valves P Code Size M400A (VB)
a
M800A (VB)
a
M1500A (VB)
a
a
Do not use M1500A on VB-7323 three-way valves.
VB-7312-0-4-P
VB-7313-0-4-P
VB-7314-0-4-P
VB-7315-0-4-P
-02, -04 1/2” (15 mm) 250 (1712) 250 (1712) —
-06 3/4” (20 mm) 198 (1356) 250 (1712) —
-08 1” (25 mm) 92 (630) 207 1418) —
-09 1-1/4” (32 mm 56 (384) 130 (890) —
10 1-1/2” (40 mm) 37 (253) 88 (603) —
-11 2” (50 mm) 19 (130) 48 (329) —
VB-7323-0-4-P
-04, -06, -08, -09,
-10, -11
1/2” to 2” 250 (1712) Do Not Use
a