Valve and Actuator Selection Procedure
1. Determine the required flow coefficient (Cv/kvs).
Using the required flow and pressure drop for the application (consult CA28, F-13755 if necessary), determine the required flow
coefficient.
2. Determine valve body part number.
Select a two-way valve body from Table-1 or a three-way mixing or diverting valve body from Table-2 having the required flow
coefficient, size, body pattern, end connection, and temperature/pressure ratings appropriate for the application.
3. Select the Forta Actuator
Using the required close-off pressure for the application, consult Table-5 and select a Forta actuator having sufficient close-off
pressure on the valve body selected in Step 2. Additional Forta actuator specifications may be found in Table-3 or in the Forta
Installation Instructions sheets shown in Applicable Literature.
4. Determine Assembly Part Number
If a complete valve and actuator assembly is required, consult Table-3 for the actuator code of the Forta actuator selected in
Step 3. For the complete assembly part number:
Change the valve body part number prefix from VB to VU.
Insert the actuator code in the third field of the part number.
Confirm the availability of the factory assembly by consulting Table-6 (two-way valves), Table-7 (three-way mixing valves),
or Table-8 (three-way diverting valves).
Example:
Valve body: VB-7213-0-4-4
Actuator: M400A-VB (actuator code 674 from table 3)
Complete assembly: VU-7213-674-4-4
Forta actuators are field configured for the desired control signal type and range plus the desired action. Consult the appropriate
Forta Installation Instructions for further information (see Applicable Literature, F-27599).