Brochure

Table Of Contents
57F-27855-10
3-Way Mixing & Diverting/Sequencing 1½” & 2” Globe Valves with Pneumatic Actuators
Effective Area (stroke)
50 Sq. In. (½ In.)
Valve Linkage VB-7313-0-4-P AV-430
Valve Linkage VB-7323-0-X-P AV-430
Positive Positioner AK-42309-500
Factory Assembly with Positive Positioner
No Yes Yes
Actuator Code (XXX)
611 612 613
Actuator MK-6601 MK- 6611 MK-6621
Spring Range (psig)
3…8 5…10 8…13
Actuator Close-Off Pressure Rating (psi)
abc
Supply Air Pressure (psig)
15/20 15 20 15/20 15 20 15/20 15 20
Stem Position
d
SU SD SD SU SD SD SU SD SD
Valve Assembly Valve Body
P
Code
Size
in.
-
VK-7313-XXX-4-P
VK4-7313-XXX-4-P
VB-7313-0-4-P
VB-7314-0-4-P
-10
40 170 250 80 110 230 170 30 160
-11 2
20 90 160 50 60 120 90 15 90
VK-7323-XXX-4-P
VK4-7323-XXX-4-P
VB-7323-0-4-P
-10
250
-11 2
a - Close-off ratings for mixing or sequencing valves: (SU = “A”, SD = “B” port). “A” port (SU) ratings equal pressure at port “A” minus pressure at port
“B”. “B” port (SD) ratings equal pressure at port “B” minus pressure at port “A”. Close-off ratings in the table are true only when the indicated supply
air pressure is applied to the actuator. A change in air pressure at the actuator alters the actual close-off pressure.
b - Close-off pressure ratings describe only the differential pressure which the actuator can close-off to standards with adequate seating force.
Consult valve body specifications for other limitations.
c - Mixing valves can be used in a diverting application but diverting valves can not be used in mixing applications.
d - SU- Stem Up; SD- Stem Down. Refer to Pg. 29, 2. VB-7000 Series ½"…2" Globe Valves for flow pattern, port designations and normal position.
1½"…2" 3-Way Mixing & Diverting/
Sequencing with Pneumatic
Actuators
3. VB-7000 Valve/Actuator
Assemblies
3. VB-7000 Valve/Actuator
Assemblies