Brochure

Table Of Contents
53F-27855-10
½"…2" 3-Way Globe Valves
with Linked NSR Actuators
MORE INFO
Scan the QR code or visit the link
below for more information.
Visit:
http://goo.gl/BnGiYc
Note: Choose a valve assembly having a close-off pressure capability sufficient for the application. Not all valve body and actuator combina-
tions are available factory-assembled. Some combinations must be field-assembled.
3. VB-7000 Valve/Actuator
Assemblies
Selection Table – 3-Way Linked Globe Valve Assemblies with Non-Spring Return Actuators
3-Way Non-Spring Return
Linked Globe Valve Assemblies
f
Actuator Torque Rating (minimum)
44 lb-in
(5 N-m)
88 lb-in
(10 N-m)
133 lb-in
(15 N-m)
Actuator Model (Actuator Code)
Floating
MF41-6043
Proportional
MS41-6043
Floating
MF41-6083
Proportional
MS41-6083
Floating
MF41- 6153
Proportional
MS41- 6153
Note: Not all factory actuator codes are available.
Linkage Kit Part Number
AV- 611
Valve Assembly
Part Number
a
P Code
Valve Size
in. (mm)
Cv
b
kvs
b
Actuator Close-off Pressure psi
ce
Vx-7313-xxx-4-P
02
½ (15)
2.2 1.9
225 -
-
04 4.4 3.8
06 ¾ (20) 7.5 6.5
08 1 (25) 14.0 12.0 100 180
09 1¼ (32) 20.0 17 60 120
10 1½ (40) 28 24 40 75 140
11 2 (50) 41 36 20 40 80
Vx-7323-xxx-4-P
02
½ (15)
2.2 1.9
250 -
04 4.4 3.8
06 ¾ (20) 7.5 6.5
08 1 (25) 15.0 13.0
09 1¼ (32) 20.0 17.3
10 1½ (40) 28 24.2
11 2 (50) 40 34.6
a - To determine a specific part number, see Pg. 46, Assembly Ordering Linked VB-7000 SmartX
Globe Valves for the relevant part series.
b - kvs = m
3
/h (∆P = 100 kPa) kvs = Cv / 1.156 Cv = kvs x 1.156
c - Mixing Valves A port seat leakage ANSI IV, B port seat leakage ANSI III, Diverting Valves seat
leakage is ANSI III.
e - Dual actuators are not available as factory assemblies.
Some factory assembly may be available but components may be ordered separately for field assembly.
f - Shown for field assembly.
3. VB-7000 Valve/Actuator
Assemblies