Brochure

Table Of Contents
F-27855-1052
½"…2" 2-Way Globe Valves
with Linked NSR Actuators
Selection Table – 2-Way Linked Globe Valve Assemblies with Non-Spring Return Actuators
2-Way Non-Spring Return
Linked Globe Valve Assemblies
f
45
90
90

steel bodies to -06 are available with
󰀨
Actuator Torque Rating (minimum)
44 lb-in. (5 N-m) 88 lb-in. (10 N-m) 133 lb-in. (15 N-m)
Actuator Model (Actuator Code)
Floating
MF41-6043
Proportional
MS41-6043
Floating
MF41-6083
Proportional
MS41-6083
Floating
MF41- 6153
Proportional
MS41- 6153
Note: Not all factory actuator codes are available.
f
Linkage Kit Part Number
AV- 611
Valve Assembly
Part Number
a
P
Code
Valve Size
in. (mm)
Cv
b
kvs
b
Actuator Close-off Pressure psi
cd
Single Actuator
Vx-7211-xxx-4-P
Vx-7213-xxx-4-P
Vx-7214-xxx-4-P
Vx-7221-xxx-4-P
Vx-7223-xxx-4-P
Vx-7224-xxx-4-P
Vx-7253-xxx-4-P
Vx-7263-xxx-4-P
Vx-7273-xxx-4-P
Vx-7283-xxx-4-P
01
½ (15)
0.4 0.3
225 -
-
02 1.3 1.1
03 2.2 1.9
04 4.4 3.8
05
¾ (20)
5.5 4.8
06 7.5 6.5
07
1 (25)
10.0 8.7
100 130
08 14.0 12
09 1¼ (32) 20.0 17 60 100
Vx-7213-xxx-4-P
Vx-7223-xxx-4-P
10 1½ (40) 28.0 24 40 70 140
11 2 (50) 40.0 35 20 40 80
a - To determine a specific part number, see Pg. 46, Assembly Ordering Linked VB-7000 SmartX Globe Valves for the relevant part series.
b - kvs = m
3
/h (∆P = 100 kPa) kvs = Cv / 1.156 Cv = kvs x 1.156
c - All Vx-72xx leakage ratings are ANSI V to 35 psi and ANSI IV above 35 psi; with the exception of Vx-7273 and Vx-7283 (ANSI III).
d -Close-off pressure ratings describe only the differential pressure which the actuator can close-off with adequate seating force. Consult valve body specifications
for other limitations. The rating value is the pressure difference between the inlet and outlet ports.
f - Shown for field assembly.
Note: Choose a valve assembly having a close-off pressure capability sufficient for the application. Not all valve body and actuator combina-
tions are available factory-assembled. Some combinations must be field-assembled.
3. VB-7000 Valve/Actuator
Assemblies
3. VB-7000 Valve/Actuator
Assemblies