Brochure

Table Of Contents
F-27855-1048
½"…2" 2-Way Globe Valves
with Linear SR Actuators
3. VB-7000 Valve/Actuator
Assemblies
Note: Choose a valve assembly having a close-off pressure capability sufficient for the application. Not all valve body and actuator combina-
tions are available factory-assembled. Some combinations must be field-assembled.
Selection Table – 2-Way Linked Globe Valve Assemblies with Linear Series Spring Return Actuators
2-Way Linked Globe Valve Assemblies
Actuator Force Rating
105 lbf (467 N) 220 lbf (979 N)
Actuator Model (Actuator Code)
a
Two-Position
MA51-7100 (801)
MA51-7101 (801)
MA51-7103-100 (804)
Floating
MF51-7103-100 (804)
Proportional
MS51-7103-100 (804)
MS51-7103-120
MS51-7103-130
MS51-7103-140
MS51-7103-150 (812)
MS51-7103-160 (814)
Two-Position
MA51-7200
MA51-7201
MA51-7202 (593)
Floating
MF51-7203 (593)
Proportional
MS51-7203 (593)
Valve Assembly
Part Number
bj
P Code
Valve Size in.
(mm)
Cv
c
kvs
c
Actuator Close-off Pressure psi
de
N.O.
f, j
N.C.
g, j
-
Vx-72x1-xxx-4-P
Vx-72x2-xxx-4-P
Vx-72x3-xxx-4-P
VxS-9263-0-4-P
1
½ (15)
0.4 0.3
250 250
2 1.3 1.1
3 2.2 1.9
4 4.4 3.8
5
¾ (20)
5.5 4.8
200 200
6 7.5 6.5
7
1 (25)
10.0 8.7
150 90
8 14.0 12
9 1¼ (32) 20.0 17 90 60 150
Vx-72x3-xxx-4-P
10 1½ (40) 28.0 24 60 35 100
Vx-72x3-xxx-4-P
11 2 (50) 28.0 24 60 35 100
a - Models without actuator codes are not offered as factory assemblies. Purchase the actuator and the valve body separately and field assemble. For available
factory assemblies, consult the price schedule.
b - To determine a specific part number, see Pg. 46, Assembly Ordering Linked VB-7000 SmartX Globe Valves for the relevant part series.
c - C
v
= gpm /√∆P (where P is measured in psi.)
k
vs
= C
v
/ 1.156
d - Close-off ANSI IV (.01%) for soft seats.
e - Close-off pressure ratings describe only the differential pressure which the actuator can close-off with adequate seating force. Consult valve body specifications
for other limitations. The rating value is the pressure difference between the inlet and outlet ports.
f - Normally open (N.O.) assembly using stem up open valve body.
g - Normally closed (N.C.) assembly using stem up closed valve body.
j - Valve body and actuator size determine the close-off capabilities. Example: All ½”, 2-Way globe valves will make the same close-off regardless of the Cv rating
for a given actuator.