Brochure

Table Of Contents
F-27855-1034
Brass Trim Threaded with Soft Seats
2-Way Brass Trim
Threaded NPT Threaded NPT
Series Part Number
VB-7213-0-4- VB-7223-0-4-
Pipe Sizes
½"…2"
Stem Action
Up Open Up Closed
ANSI Pressure Class
250 psi (up to 400 psi below 150°F)
ANSI Seat Leakage
c
󰀨
term seat leakage dependent on proper water conditioning maintenance

Control Media and Temperature

low pressure, saturated, treated steam
Flow Curve

Allowable ΔP for Water
b
87 psi (600 kPa) Max. for normal life
a
Max. inlet pressure,
saturated steam
35 psi (240 kPa)
Max ΔP for sizing,
saturated steam
b
80% of inlet pressure up to 15 psig and 42% of absolute
(gage pressure plus 14.7) inlet pressure above 15 psig inlet
Max ΔP at close-off,
saturated steam
b
󰀨-
sure)
Size Cv Kvs
Rangeability
greater than
Valve Body Part Numbers
½”
0.4 0.3
100:1
VB-7213-0-4-01 VB-7223-0-4-01
1.3 1.1 VB-7213-0-4-02 VB-7223-0-4-02
2.2 1.9 VB-7213-0-4-03 VB-7223-0-4-03
4.4 3.8 VB-7213-0-4-04 VB-7223-0-4-04
¾”
5.5 4.8 VB-7213-0-4-05 VB-7223-0-4-05
7.5 6.5 VB-7213-0-4-06 VB-7223-0-4-06
1”
10 8.7 VB-7213-0-4-07 VB-7223-0-4-07
14 12.1 VB-7213-0-4-08 VB-7223-0-4-08
1¼” 20 17.3 VB-7213-0-4-09 VB-7223-0-4-09
1½” 28 24.2 VB-7213-0-4-10 VB-7223-0-4-10
2” 40 34.6 VB-7213-0-4-11 VB-7223-0-4-11
a - To minimize noise, ensure the flow rate in the piping is less than 10 ft (3m) / second and the
differential pressure is less than 35 psi (241 kPa). Operating with differential pressures above 35
psi may result in additional noise but is acceptable up to 87 psi (600 kPa). Operating within the
cavitation zone may result in noise and internal valve damage.
b - Maximum recommended differential pressure in open position. Do not exceed recommended
differential pressure (pressure drop), as integrity of parts may be affected.
c - Refer to Seat Leakage Classes table.
2-Way Brass Trim
Valves with Soft Seats
2. VB-7000 Series
½"…2" Globe Valves
2. VB-7000 Series ½"…2"
Globe Valves
Seat Leakage Classes
ANSI/FCI 70-2
Leakage Class
Maximum Seat Leakage
Class II
0.5% of rated Cv
Class III
0.1% of Rated Cv
Class IV
0.01% of Rated Cv
Class V
0.0005 ml per minute per inch of
󰀨