Brochure

Table Of Contents
F-27855-10242
MP2000-SRU/SRD/NSR
Multi-Signal Actuators
11. Pressure Independent
Balancing and Control Valves
and Actuators
MP2000-SRU/SRD/NSR
Product Description
MP2000 SRU/SRD/NSR Actuators with spring return safety
function and non-spring return are for fine regulation of large
control valves under the demand of the HVAC controller.
MP2000 SR can be controlled by either a modulating or a
3-point control signal and is used specifically with the VP221x
SmartX PIBCV valves.
Features
Manual operation mechanical and/or electrical
Position indication, LED signalization
Selectable speed 4 or 6 s/mm (3 or 6 s/mm NSR)
Automatic Stroke Calibration
Linear to EQ% Curve Adaptation
Anti-oscillation function
Voltage or current output signal U
Auto detection of Y signal
3-point or modulating control selection
Thermal and overload protection
Precise regulation and fast response on floating signal (0.01 s)
Specifications
Nominal voltage
24 Vac/Vdc, 50 Hz/60
Hz
Power consumption 15 VA (24 V)
Control input signal
Modulating or 3-point
floating
Power Supply
Frequency
24 Vac/dc; +10 … –15
%; 50/60 Hz
Control input Y 0 … 10 V (2 … 10 V)
Ri = 40 kΩ
0 … 20 mA (4 … 20 mA)
Ri = 500 Ω
Output U
(Position Feedback)
0 … 10 V (2 … 10 V)
10kΩ
0…20 mA (4…20 mA)
510 Ω
Force 2000 N (450 lbf)
Stroke 50 mm (2”)
Speed (selectable) 4 or 6 s/mm
Max. medium temperature 200 °C (392 °F)
Ambient temperature 0 … + 55 °C
(32…131 °F)
Storage and transport
temperature
−40 … +70 °C (-40…
158 °F)
(storing for 3 days)
Humidity 5…95%
Protection class III safety extra-low
voltage
Grade of enclosure IP 54, NEMA Type 2
Weight 8.6 kg (18.96 lbs)
6.26 kg NSR (13.8 lbs)
Safety function Ye s
Safety fuction runtime 50mm stroke 120 s
Manual operation Electrical and
Mechanical
Power failure response
MP2000-SRD Safety function:
MP2000-SRU Safety function:
stem extends down
stem retracts up
Standards/Directives
Heat
Humidity
Cold
Vibration
IEC 60068-2-2
IEC 60068-2-3
IEC 60068-2-1
IEC 60068-2-6
Regulatory Compliance: c-UL-us LISTED mark compliance per
UL 60730-1 & -2-14 and CAN/CSA E60730-1 & -2-14. CE mark
compliance per directives [2014/35/EU] LVD, [2014/30/EU] EMC,
and [2011/65/EU] RoHS2. RCM mark compliance for Australia/New
Zealand community.
Part Numbers
Part No. Spring Return Direction
MP2000-SRD Stem down, extends (valve closed)
MP2000-SRU Stem up, retracts (valve open)
MP2000-NSR Non-Spring Return
Dimensions mm (inch)
Min. 450 (17.71)
186 (7.32)
191 (7.52)
369 (14.52)
353 (13.89)
schneider-electric.com | 1
Specification Sheet
MP2000-SRU/SRD/NSR
Spring Return Multi-Signal Actuators for
VP221 SmartX PIBCV, DN125-150 (5”6”)
© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. November, 2018 tc
Document Number: F-27969-3
www.schneider-electric.com
11. Pressure Independent Balancing
and Control Valves and Actuators