21F-27855-10
1. Damper Actuators
14 | schneider-electric.com Actuators Product Family Matrix - North America
F-27986-7
Part Number
Torque
lb-in (N-m)
Actuator Inputs Outputs Approximate Timing in sec. @ 70°F
Control Voltage VA @ 60Hz Feedback Auxiliary Switch Powered
MF41-6043
44 (5)
Floating
24 Vac
2.3
90
MF41-6083
88 (10) 125
MF41-6083-502
2-SPDT
MS41-6043
44 (5)
0…10 vdc 3.3 0…10 vdc
90
MS41-6083
88 (10) 125
MS41-6083-502
2-SPDT
Mx41-60x3 Series
44 lb-in and 88 lb-in Direct Coupled Damper Actuators
Product Description
These direct coupled 24 Vac Non-Spring Return rotary electric
SmartX Actuators are designed for three position (floating) control of
dampers.
Features
Compact, lightweight design.
Easy-to-see position indicator.
Self-adapting capability for maximum flexibility in damper positioning.
Quiet, low-power operation.
Manual Override.
Plenum cable standard.
Independently adjustable dual auxiliary switches option available
(MX41-6043-5X2).
Feedback position output signal available (MS41-6043 Series).
Specifications
Control Signal
MF41-6043 — Floating three-position control, 24 Vac.
MS41-6043 — Proportional, 0 to 10 Vdc;
input resistance 100 kW.
Power Inputs
See Table.
Connections
3 ft. (0.9 m) appliance cable, 18 AWG plenum-rated leads
Electrical
Outputs
Feedback potentiometer available for
MF41-6043: 0…1000 ohms < 10 mA.
Position feedback voltage for
MS41-6043/6083: 0…10 Vdc, 1 mA.
Auxiliary Switches: Dual auxiliary switches available with
MF41-6043/6083-502, MS41-6043/6083-502, and
MS41-6083-522 when these actuators are ordered as
separate units. Auxiliary switches are not offered
with factory ball valve assemblies
Mechanical
Outputs
Travel: Normal angle of rotation is 90°, limited to a maximum
of 95°. Field adjustable to limit travel on either end of stroke.
Ambient
Temperature
Limits
Shipping and storage: -40…158 °F (-40…70 °C)
Operating: -25…130 °F (-32…55 °C) ambient.
NOTE: Check the valve operating temperature limit. The
minimum valve temperature limit is 20 °F (6.7 °C)
5…95% RH, non-condensing.
Location
NEMA Type 2 (IEC IP54)
Agency
Listings
c-UL-us LISTED per UL 873 and CAN C22.2 No.24-93. CE
compliant to directives LVD, EMC, and RoHS2.
Applicable
Literature
F-26646 Selection Guide
1. Damper Actuators
Mx41-60x3 Series 44/88 lb-in
Direct Coupled NSR Actuators