9. Zone Valves
TAC Erie™ Zone Valves
149
Modulating Spring and Non-Spring Return PopTop, Two-Way and Three-Way VM Assemblies
Flow Patterns
Piping
The three-way is only configured as normally closed. For normally open configuration to the coil, turn the valve
around. For proportional valves, set the control action (direct or reverse accordingly).
The valve should be used in a closed-loop system.
All valves must be piped so the plug closes against the direction of flow. For two-way valves, flow is from port B
to port A. For normally closed three-way valves, B is the service port and A is the bypass port. For normally open
three-way valves, A is the service port and B is the bypass port.
Three-way VM valves must be piped in a mixing configuration, not diverting.
CAUTION: Do not use VM series valves in "open" systems. Excess make-up water may cause damage to the
valve.
Follow proper water treatment practices and system procedures. Refer to document F-26080; EN205,
Water and
Steam System Guidelines.
Note:
Normally open actuators are not to be used on three-way valves to achieve normally open configurations.
Use a normally closed actuator and pipe as shown in Figure-2.
Figure 1 Two-Way Valve Normally Closed. Figure 2 Two-Way Valve Normally Open.
Figure 3 Three-Way Valve
B Port Piped to Coil Outlet
Normally Closed.
Figure 4 Three-Way Valve
A Port Piped to Coil Outlet
Normally Open