Brochure

Table Of Contents
187F-27855-10
9. Zone Valves
Actuator Code Table
Operation Model Description
2-Way NPT
AP33A000
0…10 Vdc
4…20 mA field
selectable
3-Way NPT
2-Way Sweat
TAC ErieZone Valves
Three-Way Mixing Spring Return
133
For normally open, reverse pipe A and B ports. B port is normally closed.
Flow Type
Material
Body
Seat
Stem
Paddle/Plug
Fluid Temperature
Maximum Static Pressure
Seat Leakage
1/2to1in.NPTEnds
Three-WayMixingSpringReturn
Modulating
NormallyClosed(BPort)
1 to 4 Cv equal % 7.5/8 Cv linear
Forged brass
Brass
Nickel plated brass
Highly saturated nitrile
32 to 200 °F @ 104 °F ambient
(0 to 93 °C @ 40 °C)
400 psi (20.6 bar)
ANSI
IV
Size
in.
Cv (K
vs
)
Close Off Pressure
psi (kPa)
Floating With
Timeout 24 Vac
Proportional
a
0-10 V, 4-20 mA
a
Factory proportional control signal is direct-acting. An increase in control signal will open B port and close A port.
Spring Close
Motor
Close
1/2
1 (0.8) 50 (344) 50 (344) VM3221T13A00T VM3221P13A000
2 (1.7) 20 (138) 50 (344) VM3222T13A00T VM3222P13A000
4 (3.5) 20 (138) 35 (241) VM3223T13A00T VM3223P13A000
3/4
2 (1.7) 20 (138) 50 (344) VM3322T
13A00T VM3322P13A000
4 (3.5) 20 (138) 35 (241) VM3323T13A00T VM3323P13A000
7.5 (6.5) 15 (103) 35 (241) VM3327T13A00T VM3327P13A000
1 8 (6.9) 15 (103) 35 (241) VM3427T13A00T VM3427P13A000
Actuator Code Table.
Actuator Model Description
AT13A00T
3-Wire Floating with
Timeout
AB
Flow Pattern
Zone Valves
F-27411-3 © Copyright 2007 TAC. All Rights Reserved
3-Way Flow Pattern
2-Way NSR Modulating
3-Way NSR Mixing
Erie™ ½"…1" NPT 2-Way
Modulating & 3-Way Mixing NSR
TAC Erie™ Zone Valves
Two-Way Non-Spring Return
131
Flow Type
Material
Body
Seat
Stem
Paddle/Plug
Fluid Temperature
Maximum Static Pressure
Seat Leakage
1/2to1in.NPTEnds
Two-WayNon-SpringReturn
Modulating
1 to 4 Cv equal %; 7.5/8 Cv linear
Forged brass
Brass
Nickel plated brass
Highly saturated nitrile
32 to 200 °F @ 104 °F ambient
(0 to 93 °C @ 40 °C)
400 psi (20.6 bar)
ANSI IV
Size
in.
Cv (K
vs
)
Close Off Pressure
psi (kPa)
Motor Close
Floating With
Timeout 24 Vac
Floating
Requires
Thermostat/Controller
with Timeout. 24 Vac
Proportional
a
0-10 V, 4-20 mA
a-Factory proportional control signal is direct-acting. An increase in control signal will open this model.
1/2
1 (0.8) 50 (344) VM2221T33A00T VM2221T33A000 VM2221P33A000
2 (1.7) 50 (344) VM2222T33A00T VM2222T33A000 VM2222P33A000
4 (3.5) 35 (241) VM2223T33A00T VM2223T33A000 VM2223P33A000
3/4
2 (1.7) 50 (344) VM2322T33A00T VM2322T33A000 VM2322P33A000
4 (3.5) 35 (241) VM2323T33A00T VM2323T33A000 VM2323P33A000
7.5 (6.5) 35 (241) VM2327T33A00T VM2327T33A000 VM2327P33A000
1 8 (6.9) 35 (241) VM2427T33A00T VM2427T33A000 VM2427P33A000
Actuator Code Table.
Actuator Model
Description
Wiring Diagrams Dimension Information
Page Figure Page Figure
AP33A000
0 to 10 Vdc
4 to 20 mA
field selectable
331 8 386 114
Zone Valves
F-27411-3 © Copyright 2007 TAC. All Rights Reserved
TAC Erie™ Zone Valves
Two-Way Non-Spring Return
131
Flow Type
Material
Body
Seat
Stem
Paddle/Plug
Fluid Temperature
Maximum Static Pressure
Seat Leakage
1/2to1in.NPTEnds
Two-WayNon-SpringReturn
Modulating
1 to 4 Cv equal %; 7.5/8 Cv linear
Forged brass
Brass
Nickel plated brass
Highly saturated nitrile
32 to 200 °F @ 104 °F ambient
(0 to 93 °C @ 40 °C)
400 psi (20.6 bar)
ANSI IV
Size
in.
Cv (K
vs
)
Close Off Pressure
psi (kPa)
Motor Close
Floating With
Timeout 24 Vac
Floating
Requires
Thermostat/Controller
with Timeout. 24 Vac
Proportional
a
0-10 V, 4-20 mA
a-Factory proportional control signal is direct-acting. An increase in control signal will open this model.
1/2
1 (0.8) 50 (344) VM2221T33A00T VM2221T33A000 VM2221P33A000
2 (1.7) 50 (344) VM2222T33A00T VM2222T33A000 VM2222P33A000
4 (3.5) 35 (241) VM2223T33A00T VM2223T33A000 VM2223P33A000
3/4
2 (1.7) 50 (344) VM2322T33A00T VM2322T33A000 VM2322P33A000
4 (3.5) 35 (241) VM2323T33A00T VM2323T33A000 VM2323P33A000
7.5 (6.5) 35 (241) VM2327T33A00T VM2327T33A000 VM2327P33A000
1 8 (6.9) 35 (241) VM2427T33A00T VM2427T33A000 VM2427P33A000
Actuator Code Table.
Actuator Model
Description
Wiring Diagrams Dimension Information
Page Figure Page Figure
AP33A000
0 to 10 Vdc
4 to 20 mA
field selectable
331 8 386 114
Zone Valves
F-27411-3 © Copyright 2007 TAC. All Rights Reserved
TAC Erie™ Zone Valves
Two-Way Non-Spring Return
131
Flow Type
Material
Body
Seat
Stem
Paddle/Plug
Fluid Temperature
Maximum Static Pressure
Seat Leakage
1/2to1in.NPTEnds
Two-WayNon-SpringReturn
Modulating
1 to 4 Cv equal %; 7.5/8 Cv linear
Forged brass
Brass
Nickel plated brass
Highly saturated nitrile
32 to 200 °F @ 104 °F ambient
(0 to 93 °C @ 40 °C)
400 psi (20.6 bar)
ANSI IV
Size
in.
Cv (K
vs
)
Close Off Pressure
psi (kPa)
Motor Close
Floating With
Timeout 24 Vac
Floating
Requires
Thermostat/Controller
with Timeout. 24 Vac
Proportional
a
0-10 V, 4-20 mA
a-Factory proportional control signal is direct-acting. An increase in control signal will open this model.
1/2
1 (0.8) 50 (344) VM2221T33A00T VM2221T33A000 VM2221P33A000
2 (1.7) 50 (344) VM2222T33A00T VM2222T33A000 VM2222P33A000
4 (3.5) 35 (241) VM2223T33A00T VM2223T33A000 VM2223P33A000
3/4
2 (1.7) 50 (344) VM2322T33A00T VM2322T33A000 VM2322P33A000
4 (3.5) 35 (241) VM2323T33A00T VM2323T33A000 VM2323P33A000
7.5 (6.5) 35 (241) VM2327T33A00T VM2327T33A000 VM2327P33A000
1 8 (6.9) 35 (241) VM2427T33A00T VM2427T33A000 VM2427P33A000
Actuator Code Table.
Actuator Model
Description
Wiring Diagrams Dimension Information
Page Figure Page Figure
AP33A000
0 to 10 Vdc
4 to 20 mA
field selectable
331 8 386 114
Zone Valves
F-27411-3 © Copyright 2007 TAC. All Rights Reserved
TAC Erie™ Zone Valves
Three-Way Mixing Non-Spring Return
135
Flow Type
Material
Body
Seat
Stem
Paddle/Plug
Fluid Temperature
Maximum Static Pressure
Seat Leakage
1/2to1in.NPTEnds
Three-WayMixing
Non-SpringReturn
Modulating
1 to 4 Cv equal % 7.5/8 Cv linear
Forged brass
Brass
Nickel plated brass
Highly saturated nitrile
32 to 200 °F @ 104 °F ambient
(0 to 93 °C @ 40 °C)
400 psi (20.6 bar)
ANSI IV
Size
in.
Cv (K
vs
)
Close Off Pressure
psi (kPa)
Motor Close
Floating With
Timeout 24 Vac
Floating
Requires
Thermostat/Controller
with Timeout. 24 Vac
Proportional
a
0-10 V, 4-20 mA
1/2
1 (0.8) 50 (344) VM3221T33A00T VM3221T33A000 VM3221P33A000
2 (1.7) 50 (344) VM3222T33A00T VM3222T33A000 VM3222P33A000
4 (3.5) 35 (241) VM3223T33A00T VM3223T33A000 VM3223P33A000
3/4
2 (1.7) 50 (344) VM3322T33A00T VM3322T33A000 VM3322P33A000
4 (3.5) 35 (241) VM3323T33A00T VM3323T33A000 VM3323P33A000
7.5 (6.5) 35 (241) VM3327T33A00T VM3327T33A000 VM3327P33A000
1 8 (6.9) 35 (241) VM3427T33A00T VM3427T33A000 VM3427P33A000
Actuator Code Table.
Actuator Model
Description
AP33A000
0 to 10 Vdc
4 to 20 mA
field selectable
AB
Flow Pattern
Zone Valves
F-27411-3 © Copyright 2007 TAC. All Rights Reserved
a-
Factory proportional control signal is direct-acting. An increase in control signal will open B port and close A port.
Erie™ ½"…1¼" Sweat Ends 2-Way NSR Modulating
TAC Erie Zone Valves
Two-Way Non-Spring Return
130
Flow Type
Material
Body
Seat
Stem
Paddle/Plug
Fluid Temperature
Maximum Static Pressure
Seat Leakage
1/2to1-1/4in.SweatEnds
Two-WayNon-SpringReturn
Modulating
1 to 4 Cv equal %; 7.5/8 Cv linear
Forged brass
Brass
Nickel plated brass
Highly saturated nitrile
32 to 200 °F @ 104 °F ambient
(0 to 93 °C @ 40 °C)
400 psi (20.6 bar)
ANSI IV
Size
in.
Cv (K
vs
)
Close Off Pressure
psi (kPa)
Motor Close
Floating With
Timeout 24 Vac
Floating
Requires
Thermostat/Controller
with Timeout. 24 Vac
Proportional
a
0-10 V, 4-20 mA
a-Factory proportional control signal is direct-acting. An increase in control signal will open this model.
1/2
1 (0.8) 50 (344) VM2211T33A00T VM2211T33A000 VM2211P33A000
2 (1.7) 50 (344) VM2212T33A00T VM2212T33A000 VM2212P33A000
4 (3.5) 35 (241) VM2213T33A00T VM2213T33A000 VM2213P33A000
3/4
2 (1.7) 50 (344) VM2312T33A00T VM2312T33A000 VM2312P33A000
4 (3.5) 35 (241) VM2313T33A00T VM2313T33A000 VM2313P33A000
7.5 (6.5) 35 (241) VM2317T33A00T VM2317T33A000 VM2317P33A000
1
4 (3.5) 35 (241) VM2413T33A00T VM2413T33A000 VM2413P33A000
8 (6.9) 35 (241) VM2417T33A00T VM2417T33A000 VM2417P33A000
1-1/4 8 (6.9) 35 (241) VM2517T33A00T VM2517T33A000 VM2517P33A000
Actuator Code Table.
Actuator Model
Description
Wiring Diagrams Dimension Information
Page Figure Page Figure
AP33A000
0 to 10 Vdc
4 to 20 mA
field selectable
331 8 386 114
Zone Valves
© Copyright 2007 TAC. All Rights Reserved F-27411-3
-
verse pipe A and B ports.

9. Zone Valves