Brochure

Table Of Contents
167F-27855-10
VB-2000 Series Ball Valves
with SmartX Actuators
16 | schneider-electric.com Selection Guide
January, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Document Number: F-27086-14
Table-11. Actuator Specifications
Inputs
Control Signal
MA40-704x: ON/OFF SPST control contacts or Triacs (500 mA rated).
MS40-7043: Proportional, 2 to 10Vdc or 4 to 20 mAdc with 500 ohm resistor.
MS40-7043 MP/MP5: Proportional 6 to 9 Vdc.
MF40-7043: Floating point control, 24 Vac.
Power Requirements
All 24 Vac circuits are Class 2
Part Number
Voltage 50/60
Hz
Voltage
Vdc
Running Holding
50 Hz 60 Hz 50 Hz 60 Hz
VA W VA W W W
MA40-7043
24 Vac ± 20% 22 to 30
4.4 2.9 4.4 2.9 0.8 0.8
MS40-7043 5.6 4.2 5.6 4.2 2.4 2.4
MF40-7043 5.9 4.4 5.9 4.4 2.9 2.9
MS40-7043-MP
6.9 5.0 6.6 5.0 3.2 3.2
MS40-7043-MP5*
MA40-7040*
120 Vac ±
10%
- 6.4 3.8 4.3 3.4 1.6 1.2
Connections
MA40-704x and MA40-704x-501: 3 ft. (0.9 m) long, appliance cable, 1/2 in. conduit connector. For M20 Metric
conduit, use AM-756 adaptor.
MF40-7043 and MF40-7043-501, MS40-7043 and MS40-7043-501: 3 ft. (0.9 m) long, plenum rated cable, 1/2 in.
conduit connector. For M20 Metric conduit, use AM-756 adaptor..
Motor Type
MA40-704x: Brush DC.
MF40-7043, MS40-7043: Brushless DC.
Outputs
Electrical
Auxiliary Switches: Available when actuators are ordered as separate units. Auxiliary switches are not offered
with factory ball valve assemblies.
Mx40-7043-501 and MS40-7043-MP5:
One auxiliary switch available. SPDT 6 A resistive @ 24
Vac, adjustable 0 to 95° (0 to 1 scale). Switch meets
VDE requirements for 6 (1.5) A, 24 Vac.
MA40-7040-501:
One auxiliary switch available. SPDT 6 A resistive @
250 Vac, adjustable 0 to 95° (0 to 1 scale). Switch
meets VDE requirements for 6 (1.5) A, 250 Vac.
Position Feedback Voltage: For 2 to 10 Vdc proportional actuators, the feedback signal is the same voltage
range as the input signal. The feedback signal can supply up to 0.5 mA to operate up to four additional slave
actuators.
Control Mode: Switch provided for selection of direct acting or reverse acting control mode on proportional
models.
Timing: MA-704x - Approx. 50 sec.; MF- and MS-7043 - Approx. 130 sec.
Auxiliary Power Supply: MS40-7043-MP and MS40-7043-MP5 - +20 Vdc @ 25 mA (max.).
Mechanical
Stroke: Angle of rotation is limited to a maximum of 95°, with mechanical stop.
Output torque rating: Mx40-704x - 44 lb-in (5 N-m).
Position indicator: Visual scale numbered from 0 to 90°, provided for position indication.
Environment
Temperature Limits
Shipping and storage: -40 to 160 °F (-40 to 71 °C) ambient.
Operating: -22 to 140 °F (-30 to 60 °C) ambient.
NOTE: Check the valve operating temperature limit. The minimum valve temperature limit is 20 °F (6.7 °C)
Humidity 5 to 95% RH, non-condensing.
Locations NEMA 2, UL Type 2 (IEC IP54)
Agency Listings (Actuator)
UL UL 873, Underwriters Laboratories (File #9429 Category Temperature-Indicating and Regulating Equipment).
cUL Canadian Standards C22.2 No. 24-93.
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
Australia
This product meets requirements to bear the RCM mark according to the terms specified by the Communica-
tions Authority under the Radiocommunications Act 1992.
* Not available as an assembly.
Assemblies with Mx40-704x SR SmartX Actuators
Assemblies with Mx40-704x SR SmartX Actuators
8. VBB/VBS and VB-2000 Series
Ball Valve Assemblies
8. VBB/VBS and VB-2000 Series
Ball Valve Assemblies