Brochure

Table Of Contents
149F-27855-10
Mx1…Mx3 A0x
Series Actuators
4 | schneider-electric.com Selection Guide
February, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Document Number: F-27395-15
Product Selection: Actuators
Table-1: Two-Position Actuators
Part
Number Control Signal
Spring Return
Action (Valve
Normal Position)
VA / Voltage Leads
Stroke
Timing
g
Spring
Return
Timing
g
End
Switch
M210A00
Two-Position
Normally Open
3.5/1.8 at 24 Vac/24
Vdc
Removeable Terminal Block
b
50 sec 35 sec.
M210A01
10 ft. (3.05 m) Plenum
Cable
c
M210A11 SPST
M210A02
18 in. (45 cm) Appliance
Wire
M210A12 SPST
M210M02
6.0/6.0 at 100…277
Vac, 50/60 Hz
18 in. (45 cm) Appliance
Wire
M210M12 SPST
M220A00
Normally Closed
3.5/1.8 at 24 Vac/24
Vdc
Removeable Terminal Block
b
M220A01
10 ft. (3.05 m) Plenum
Cable
c
M220A11 SPST
M220A02
18 in. (45 cm) Appliance
Wire
M220A12 SPST
M220M02
6.0/6.0 at 100…277
Vac, 50/60 Hz
M220M12 SPST
Table-2 Floating Actuators
Part Number Control Signal
Spring Return Action
(Valve Normal
Position)
VA @ 24 Vac
50/60 Hz
Leads
Stroke Time,
sec. 50/60
Hz
Time-out
Delay,
sec. 50/60 Hz
M332A00
Floating
None 2.3/2.4
Terminal Block
b
159/135 181 Sec
M332A01 10 ft. (3.05 m) Plenum Cable
c
M312A00
Normally Open
3.2/3.3
d
Terminal Block
b
M312A01 10 ft. (3.05 m) Plenum Cable
c
M322A00
Normally Closed
Terminal Block
b
M322A01 10 ft. (3.05 m) Plenum Cable
c
Table-3 Proportional Actuators
Part Number Control Signal
Spring Return Action
(Valve Normal
Position)
VA @ 24 Vac
50/60 Hz
Leads
Stroke Time,
sec. 50/60
Hz
Time-out Delay,
sec. 50/60 Hz
M333A00
Proportional
a
(Vdc : 0…5,
0…10, 2…10,
5…10, 4…20 mA
dc
e
)
None 2.7/2.8
Terminal Block
b
159/135
200/166
M333A01 10 ft. (3.05 m) Plenum Cable
c
145 Sec
M313A00
Normally Open
2.7/2.8
d
Terminal Block
b
M313A01 10 ft. (3.05 m) Plenum Cable
c
M323A00
Normally Closed
Terminal Block
b
M323A01 10 ft. (3.05 m) Plenum Cable
c
a. Default congured for 0…10 Vdc input signal, direct acting control.
b. All terminal block and appliance wire units accept a 1/2” conduit connector tting (.875” diameter).
c. All plenum cable units include an integral 3/8” conduit connector tting.
d. Size transformer for 10 VA per actuator.
e. For 4…20 mA control, a separate isolated transformer must be used with each valve.
g. Nominal.
8. VBB/VBS and VB-2000 Series
Ball Valve Assemblies
8. VBB/VBS and VB-2000 Series
Ball Valve Assemblies