Brochure

Table Of Contents
147F-27855-10
8. VBB/VBS and VB-2000 Series
Ball Valve Assemblies
2 | schneider-electric.com Selection Guide
February, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Document Number: F-27395-15
Speccations
Actuator
Voltage 24 Vac for oating and proportional
100…277 Vac for two position multi-voltage
types
Power
Requirements
See Table-1, Table-2, and Table-3.
Control Signal 2-Position, Floating, or Proportional; half wave
rectied power supply
Timing, Full Open
to Full Close
See Table-1, Table-2 and Table-3.
Manual Operating
Lever / Position
Indicator
Standard on all models.
Auxiliary End
Switch (optional)
SPST 24 Vac/Vdc, 101 mA…5 A max.
Materials Thermoplastic base and cover.
Approved for use in air plenums.
Shipping & Storage
Temperature Limit
-40…169 °F (-40…76°C).
Operating
Temperature Limit
at max uid temp.
Floating 32…140 °F (0…60 °C)
Proportional 32…140 °F (0…60 °C)
Two-Position 32…169 °F (0…76 °C)
Humidity 5…95% relative humidity,
non-condensing.
Locations NEMA 2, IEC IP31. Indoor Use Only.
Valve
Service
a
Hot and chilled water, up…60% glycol.
System Static Pressure
Limit
600 psi (4137 kPa).
Fluid Temperature Limit 20…250°F (-7…121°C).
Cv (Kv) See Tables 4 through 7.
Close-o󰀨 Pressure
b
130 psi 2-Way; 70 psi 3-Way
Di󰀨erential Pressure 30 psi normal operation
20 psi quiet operation.
Seat Material PTFE
Characterized Insert Glass-lled PEEK
Seat Leakage ANSI class IV (0.01%) at both A and B
ports with pressure at inlet.
End Connections NPT threaded (VBxxNxx)
Rangeability Greater than 300:1.
Body Material Forged brass.
Stem Material Stainless steel anti-blow out stem with
dual Viton™ o-rings.
Ball Material Chrome plated brass (VBB series)
or stainless steel (VBS series).
a. Not rated for steam service.
b. Close-o󰀨 is dened as the maximum allowable pressure drop to which a valve
may be subjected while fully closed.
Agency Listings
M2 SmartX
actuators
M3 SmartX
actuators:
North America: c-UL-us LISTED per
UL 873 and C22.2 No.24.
European Union: LVD 2006/95/EC and
EMC 2004/108/EC directives compliant.
North America: c-UL-us LISTED per
UL 60730-1 & -2-14 and CSA E60730-1 & -2-14.
FCC part15 classB & ICES-003 classB emissions
compliant.
European Union: LVD 2014/35/EU and EMC
2014/30/EU directives, per EN 60730-1 & -2-14.
EN 61000-6-2 immunity & EN 61000-6-3 emissions
compliant.
Australia This product meets requirements to bear the RCM
Mark.
Plenum Rating Actuators with terminal block or plenum cable leads
are plenum rated.
CRN Number CRN OC0970.9012345678NTY.
RoHS
Compliant
VBS valves and M3/M2 actuators comply with
European Directive RoHS 2 Directive 2011/65/EU.
Please consult factory for part number specic
compliance.
REACh
Compliant
Compliant as dened in Article 33 of the REACh
Regulation (EC)1907/2006.
AAB
Supply
Return
Typical Two-Way
Fan Coil Application
Supply
Bypass
Return
B
AB A
Typical Three-Way
Fan Coil Application
Application Schematics
Typical applications
For simplicity, balancing valves and control devices are not
shown.
Mixing applications
Mx1…Mx3 A0x Series Actuator/
Valve Specifications
8. VBB/VBS and VB-2000 Series