Application
VB-9313 series 3-Way mixing valves control hot or chilled water in heating or air
conditioning systems. These valves must be piped with two inlets (“A” and “B” ports)
and one outlet (“AB” port). They are used for two-position or proportional control
applications. Valve assemblies require an actuator and a valve linkage that may be
factory or field assembled.
Features
• Valve sizes 2½”…6”.
• 125 psig pressure rating per ANSI Standards (B16.1–1993) for flanged cast iron
bodies.
• Spring-loaded TFE & EPDM packing.
VB-9313 3-Way Mixing
Valve Bodies
VB-9313-0-5-P
(Typical)
Specifications
Valve Body Series
VB-9313-0-5-P
Application
Chilled or Hot Water
c
Flow Characteristics
Mixing
Sizes
2½”…6”
Type of End Fitting
125 lb. Flanged
Valve
Materials
Body
Cast Iron
Seat
Bronze
Stem
Stainless Steel
Plug
Brass
Packing
Spring Loaded
TFE & EPDM
Disc
None
ANSI Pressure Class, psig
125 (up to 200 psig below
150°F)
Allowable Control Media Temperature, °F (°C)
40°F …300°F (4°C…149°C)
Allowable Differential Pressure, Water, psi (kPa)
a
35 psi (241 kPa) Max. for
Normal Life
Valve Size, In.
Cv
Rating
kvs
b
Rating
Stroke
Complete Valve Body
Part Number
74 64 7/8 in. (22 mm)
VB-9313-0-5-12
3 101 87 7/8 in. (22 mm)
VB-9313-0-5-13
4 170 147 7/8 in. (22 mm)
VB-9313-0-5-14
5 290 251 1¾ in. (45 mm)
VB-9313-0-5-15
6 390 337 1¾ in. (45 mm)
VB-9313-0-5-16
a - Maximum recommended differential pressure in open position. Do not exceed the
recommended differential pressure (pressure drop) or integrity of parts may be affected
Exceeding maximum recommended differential pressure voids the product warranty.
b - k
vs
= m
3
/h (P = 100 kPa) k
vs
= C
v
/ 1.156 C
v
= gpm /√∆P (in psi).
c - Glycol up to 50%
A AB
B
VB-93xx 3-Way Mixing Flow Pattern