Globe Valve Actuators & Assemblies
Forta
VB-72x3 or VB-82x3 Two Way Globe Valve, Forta Non-Spring Return, Floating Control Setup Reference
Valve Type Program Switch Position Desired Valve Operations
Valve position with D2
powered
Switch 1 Switch 2 Switch 7 Power up
position
a
Power to D2
input terminal
Feedback signal Power to D1
input terminal
Feedback signal
VB-x223 stem up closed OFF ON OFF Retract-No Flow Retract-No Flow 2 Vdc Extend-Full Flow 10 Vdc
VB-x223 stem down open OFF ON ON Retract-No Flow Extend-Full Flow 10 Vdc Retract-No Flow 2 Vdc
VB-x223 stem up closed ON ON ON Extend-Full Flow Retract-No Flow 10 Vdc Extend-Full Flow 2 Vdc
VB-x223 stem down open ON ON OFF Extend-Full Flow Extend-Full Flow 2 Vdc Retract-No Flow 10 Vdc
VB-x213 stem up open ON ON ON Extend-No Flow Retract-Full Flow 10 Vdc Extend-No Flow 2 Vdc
VB-x213 stem down closed ON ON OFF Extend-No Flow Extend-No Flow 2 Vdc Retract-Full Flow 10 Vdc
VB-x213 stem up open OFF ON OFF Retract-Full Flow Retract-Full Flow 2 Vdc Extend-No Flow 10 Vdc
VB-x213 stem down closed OFF ON ON Retract-Full Flow Extend-No Flow 10 Vdc Retract-Full Flow 2 Vdc
VB-73x3 or VB-9313 Three Way Globe Valve, Forta Non-Spring Return, Floating Control Setup Reference
Valve Type Program Switch Position Desired Valve Operations
Valve position with D2
powered
Switch 1 Switch 2 Switch 7 Power up
position
a
Power to D2
input terminal
Feedback signal Power to D1
input terminal
Feedback signal
VB-x313 stem up
Open B to AB
OFF
ON
OFF Retract-Full Flow
B to AB
Retract-Full Flow
B to AB
2 Vdc
Extend-No Flow
B to AB
10 Vdc
VB-x313 stem down
Closed B to AB
OFF ON ON Retract-Full Flow
B to AB
Extend-No Flow
B to AB
10 Vdc Retract-Full Flow
B to AB
2 Vdc
VB-x313 stem up
Open B to AB
ON ON OFF Extend-Full Flow
A to AB
Extend-No Flow
B to AB
2 Vdc Retract-Full Flow
B to AB
10 Vdc
VB-x313 stem down
Closed B to AB
ON ON
ON Extend-Full Flow
A to AB
Retract-Full Flow
B to AB
10 Vdc Extend-No Flow
B to AB
2 Vdc
VB-7323 stem up
Flow B to AB
OFF ON OFF Retract-Full Flow
B to AB
Retract-Full Flow
B to AB
2 Vdc Extend-No Flow
B to AB
10 Vdc
VB-7323 stem down
Flow B to A
OFF ON ON Retract-Full Flow
B to AB
Extend-No Flow
B to AB
10 Vdc Retract-Full Flow
B to AB
2 Vdc
VB-7323 stem up
Flow B to AB
ON ON OFF Extend-Full Flow
B to A
Extend-No Flow
B to AB
2 Vdc Retract-Full Flow
B to AB
10 Vdc
VB-7323 stem down
Flow B to A
ON ON ON Extend-Full Flow
B to A
Retract-Full Flow
B to AB
10 Vdc Extend-No Flow
B to AB
2 Vdc
VB-8303 Three Way Globe Valve, Forta Non-Spring Return, Floating Control Setup Reference
Valve Type Program Switch Position Desired Valve Operations
Valve position with D2
powered
Switch 1 Switch 2 Switch 7 Power up
position
a
Power to D2
input terminal
Feedback signal Power to D1
input terminal
Feedback signal
VB-8303 stem up
Open B to AB
OFF ON OFF Retract-Full Flow
B to AB
Retract-Full Flow
B to AB
2 Vdc Extend-No Flow
B to AB
10 Vdc
VB-8303 stem down
Closed B to AB
OFF ON ON Retract-Full Flow
B to AB
Extend-No Flow
B to AB
10 Vdc Retract-Full Flow
B to AB
2 Vdc
VB-8303 stem up
Open B to AB
ON ON OFF Extend-Full Flow
A to AB
Extend-No Flow
B to AB
2 Vdc Retract-Full Flow
B to AB
10 Vdc
VB-8303 stem down
Closed B to AB
ON ON ON Extend-Full Flow
A to AB
Retract-Full Flow
B to AB
10 Vdc Extend-No Flow
B to AB
2 Vdc
a. Upon power up, actuator will stroke to the power up position before the input signal takes control.
Note: The switch positions on pages eight and nine are the base programming configurations, in the base configurations all other switches
should be switched off. Once the base programming configuration has been set up you may wish to add additional programming features
and functions that are listed below.
DA = Full open, full flow, 10vdc output / Full closed, no flow, 2vdc output
RA = Full open, full flow, 2vdc output / Full closed, no flow 10vdc output