User Guide

F-26563-2 Copyright 2008 TAC All Rights Reserved. 9
ADJUSTMENTS
The CP-9301 and CP-9302 actuator drives feature one jumper for selecting voltage or
current input, a second jumper for selecting 3% or 5% deadband, and potentiometers for
adjusting the input span and start point. The CP-9301 is preset at the factory for voltage
input, and the CP-9302 is preset for current input (Table-1). When necessary, these factory
presets may be changed according to the procedures in this section.
Voltage Input
Adjustments
When a CP-9301 has been left at its factory presets, the settings detailed in Table-1 apply.
If a CP-9301 requires adjustments to its deadband, startpoint, or input span, or if a CP-9302
is to be reconfigured for voltage input, make adjustments according to the following:
Caution:
Do not apply a current source input to a CP-9301 or CP-9302 actuator drive that is
configured for voltage input (factory setting). Doing so may damage the drive.
Static charges produce voltages high enough to damage the electronic components.
Follow static electricity precautions when servicing the device(s).
1. Turn off the controller signal to the drive’s input.
2. Turn off power to the actuator.
3. Remove the screw that secures the cover to the drive, then remove the cover. This
provides access to the start point and input span adjustment potentiometers, as well as
the input and deadband jumpers (Figure-9).
4. Disconnect the drive’s yellow and blue leads from the controller.
5. When reconfiguring a CP-9302 for voltage input, reposition the input jumper to the
voltage input setting, as shown in Figure-9.
6. Connect the leads of a suitable voltage signal source (voltage calibrator) to the
appropriate drive leads.
7. Connect a DVM to the yellow (drive input) and blue (COM) leads of the drive.
8. Apply power to the actuator, then turn on the voltage signal source.
9. If desired, reset the deadband by repositioning the deadband jumper.
10. Adjust the voltage signal source (voltage calibrator) until the DVM reading equals the
desired start point voltage (0 to 10 Vdc).
11. With the desired start point voltage applied, adjust the start point potentiometer, using
a small screwdriver, so that the actuator shaft
just reaches the start point
.
Voltage Input
(CP-9301 Factory Preset)
3% Deadband
(Factory Preset)
Start Point
Potentiometer
Input Span
Potentiometer
Current Input
(CP-9302 Factory Preset)
5% Deadband
Alternate Jumper Settings
Figure-9 Input and Deadband Jumpers, and Input Span and Start Point Potentiometers.