User Guide
6 Copyright 2008 TAC All Rights Reserved. F-26563-2
Mounting The drive may be mounted on either the left or right side of the actuator, in a conduit opening
adjacent to the low voltage wiring compartment. Mount the drive onto an actuator as follows:
1. Remove the cover from the actuator, to expose its power wiring compartment and low
voltage wiring compartment. Note that each side of the actuator casing features two 1/2"
knockouts which provide access to these two compartments.
2. Determine on which side of the actuator the drive is to be mounted (Figure-5, Figure-6,
and Figure-10). Remove the knockout on that side, adjacent to the low voltage wiring
compartment.
3. Temporarily remove the locknut from the drive. Verify that the O-ring (Figure-6 and
Figure-10) is fully seated on the drive’s casing, and insert the drive’s 1/2" conduit
connector into the opening from which the knockout was removed.
4. Secure the drive to the actuator with the locknut removed in step 3. Refer to Figure-6.
5. Connect the drive to the actuator according to the instructions in the Wiring section.
Drive
Drive
Actuator
Left-Side Mounting
Right-Side Mounting
Figure-5 Mounting Position of Drive on Actuator.
L1 (H)
L2 (G)
Barrier
Power Wiring
Compartment
Drive
3
1
5
6
x
2
4
7
8
L2 (G)
L1 (H)
2
1
Actuator
1
3
7
5
6
4
5
1 Top view.
2 Right-side mounting is shown.
3 Alternate left-side mounting.
4 Purge override (input signal override) is available with CP-9302 only.
5 Make all connections in accordance with the electrical wiring
diagram and in accordance with national and local electrical codes.
Use copper conductors that are suitable for 105 ˚C.
6 The terminals marked L1 and L2 on 120 and 240 Vac actuators are
marked H and G on 24 Vac actuators.
7 Ground the following at the terminal block mounting screw:
the shield wire; the drive's green/yellow ground wire; and the
jumper wire from terminal X (MP-XXXX-XXX-X-2 models).
Locknut
Low Voltage
Wiring Compartment
5
To Controller
Purge Override
(Input Signal
Override)
Ground
From
Power
Source
O-Ring
Case Ground Screw
Terminal Block
Mounting Screw
(Ground)
Purge Input
(Override Input)
Purge + (Override +)
Drive Input
Common
+
_
Shield
Shield
Figure-6 Actuator/Drive Wiring and Mounting Arrangement.