User Guide

2 Copyright 2008 TAC All Rights Reserved. F-26563-2
SPECIFICATIONS
Mounting: Directly to an actuator. The drive may be mounted on either the left or right side
of the actuator, in a conduit opening adjacent to the low voltage wiring compartment.
Case: Injection molded plastic with stamped aluminum cover.
Inputs — Voltage and Current
Input: Refer to Table-1 and Adjustments Section.
Input Span Adjustment: Refer to Table-1 and Adjustments Section.
Start Point Adjustment: Refer to Table-1 and Adjustments Section.
Input Impedance:
Voltage Input, Greater than 10,000 ohms.
Current Input, 250 ohms.
Power Supply: Power shall be supplied directly from the shading coil windings provided on
the shaded pole reversible motor of the gear train actuator (less than 30 Vac).
Outputs
Connections: Color-coded leads with crimped screw terminal connectors. Purge override
(input signal override) leads are color-coded pigtails.
Shading Coil Triac Output: 1.2 A RMS.
Deadband: Refer to Table-1 and Adjustments Section.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 160 °F (-40 to 71 °C).
Operating, -40 to 136 °F (-40 to 58 °C).
Humidity: 5 to 95% relative humidity, non-condensing.
Locations: NEMA Type 4; IEC IP56.
Agency Listings
UL Listed:
UL 873 (File #E9429 Category Temperature Indicating and Regulating Equipment).
Certified for use in Canada by Underwriters Laboratories.
European Community: EMC Directive 89/336/EEC.
Table-1 Model Chart.
Part
Number
Input Signal
Override
Factory Presets Jumper Settings
Potentiometer Adjustment
Ranges
Input
Signal
Deadband
Start
Point
Input
Span
Input
Signal
Deadband Input Span Start Point
CP-9301
Not
Available
Voltage
(6 to 9 Vdc)
3% of
Input Span
6 Vdc 3 Vdc
•Voltage
or
Current
•3% or 5%
of Input
Span
3.0 to 16.5 Vdc
or
8 to 16 mAdc
0 to 10 Vdc
or
2 to 16 mAdc
CP-9302
Available
(Use is Optional)
Current
(4 to 20 mAdc)
4mAdc 16mAdc
Table-2 Typical Actuators.
Actuator
Series
Power Torque
Stroke
Degrees
Spring
Return
Internal
Transformer
a
Vac (60 Hz) Amp Lb-in. N-m
MP-2113-500 24 2.2 50 5.6 180 No
MP-361 24 2.5 50 5.6 180 CW No
MP-371 24 2.5 50 5.6 180 CCW No
MP-381 24 2.5 220 24.9 180 No
MP-9713 24 4.0 800 90.3 180 No
MP-2150-500 120 0.5 50 5.6 180 Yes
MP-465 120 0.5 50 5.6 180 CW Yes
MP-475 120 0.5 50 5.6 180 CCW Yes
a Units with a “-2” suffix, e.g. MP-XXXX-XXX-2-X, include a built-in transformer (used for TAC Microtherm
®
or with AE-504) with secondary leads wired
externally to terminals 7 (Blue, 12 Vac) and 8 (Red, 24 Vac) of the actuator.
Caution
: When using the CP-9301 or CP-9302 with actuators containing an
internal transformer
, disconnect and tape off the red and blue leads before
installing and powering the device.
Failure to do so can result in damage to the actuator drive
.
Note
: Models prior to “-2” suffix had transformer wired directly to potentiometer. To disconnect the transformer, remove the back plate of the actuator, then
disconnect and tape the transformer leads.