User Guide

F-24190-3 © Copyright 2008 TAC All Rights Reserved. 7
Wiring Requirements
Control Leads
The two input wires of the CP-8X91-456 which must be connected to the controller are
coded Black (–) and Red (+), respectively. (See Table-3 and Figure-1 through Figure-5.)
W
C A U T I O N
Use three-conductor twisted shielded wire when it becomes necessary to install the
control leads in the same conduit with power wiring or when RFI/EMI generating devices
are near.
Do not connect shield or conduit to earth ground.
Table-3 Control Wiring Data.
Power Leads
CP-8391-456: When the CP-8391-456 is mounted on an electric actuator, all power is sup-
plied by the electric actuator. (See Figure-1 through Figure-4.) Unused line voltage wire of
the CP-8391-456 drive should be clipped and carefully insulated. (See Figure-1 through
Figure-4.)
The Violet lead is power line common. The Blue lead is for 120 Vac. The Black/White lead
is for 240 Vac.
CP-8191-456: Power can be supplied by source other than the actuator. (See Figure-1
through Figure-4.) Wire to coded screw terminals.
Wire Size (GA) Maximum Wire Run in ft. (m)
18 1000 (304)
16 2250 (685)
14 4000 (1210)