User Guide

F-24190-3 © Copyright 2008 TAC All Rights Reserved. 11
Figure-10 Service Application Wiring Diagram, CP-8X91-456 to MP-4XX & MP-21XX Series and MP-9750
Actuator Connections (see Table-2 for specific actuators).
Figure-11 Service Application Wiring Diagram, CP-8X91-456 to MP-98XX & MP-99XX Series
Actuator Connections (see Table-2 for specific actuators).
Red (+)
Black (-)
Yellow (7)
Brown (4)
Orange (8)
White/Blue (3)
Red/Yellow (x)
Black/Blue (2)
Violet (COM)
Blue (120 Vac)
Black/White (240 Vac)
Diagram Shown Increasing input causes
CCW actuator rotation.
L1
L2
2
X
3
8
4
7
Slidewire
Limit
Switch
Shading Windings
Field Winding
Power (120 Vac)
Actuator Terminal
Input Volts DC Signal
from Controller
(Wire to L1 on 240 Vac actuators
and tape off Blue, 120 Vac, lead.)
CP-8391-456 Wire Color
CP-8191-456 Terminal Identification shown in ( )
*
*
*
*
*For CW rotation with
increasing input
signal, exchange
wires to terminals
7 & 8 and 2 & 3.
Note: All references to direction
of actuator shaft rotation are de-
termined by looking at the face
of the actuator with the output
shaft.
Note: For actuators with
internal transformers.
Disconnect red and blue leads
from actuator transformer to
terminals 7 and 8 and tape off.
Red (+)
Black (-)
Yellow(7)
Brown (4)
Orange (8)
White/Blue (3)
Red/Yellow (x)
Black/Blue (2)
Violet(COM)
Blue (120 Vac)
Black/White (240 Vac)
Diagram Shown Increasing input causes
CCW actuator rotation.
L1
L2
2
X
3
8
4
7
Slidewire
Limit
Switch
Power (120 Vac)
Actuator Terminal
Input Volts DC Signal
from Controller
NC
Motor
Windings
Solenoid
Brake
(Wire to L1 on 240 Vac actuators
and tape off Blue, 120 Vac, lead.)
CP-8391-456 Wire Color
CP-8191-456 Terminal Identification shown in ( )
*
*
*
*
*For CW rotation with
increasing input signal,
exchange wires to ter-
minals 7 & 8 and 2 & 3.
Note: All references to direction of
actuator shaft rotation are determined
by looking at the face of the actuator