User Guide
Table Of Contents
- Application
- Features
- Applicable Literature
- . Environmental Controls Cross-Reference Guide, F-23638
- . Environmental Controls Reference Manual, F-21683
- . Environmental Controls Application Manual, F-21335
- . Pneumatic Products Catalog, F-27383
- . MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series Reversible and Proportional Electric Actuators General Instructions, F-15479
- SPECIFICATIONS
- Inputs
- Outputs
- Environment
- Agency Listings
- Table-2 Typical Actuators.
- TYPICAL APPLICATIONS (wiring diagrams)
- INSTALLATION
- WIRING
- ADJUSTMENTS
- Start Point Adjustment
- 1. Peel back the Schneider Electric label from the drive, to expose the start point adjustment potentiometer. Refer to Figure-3.
- 2. Disconnect the red, yellow, and blue leads of the drive from the controller.
- 3. Connect the leads of TOOL-202 to the like-colored leads of the drive.
- 4. Connect a DVM to the yellow (OP1) and blue (COM) leads of the drive.
- 5. Adjust TOOL-202 until the DVM reading equals the required start point voltage (2 to 12 Vdc).
- 6. Adjust the actuator start point, using a small, single-slotted screwdriver, so that the actuator shaft just begins to rotate when the desired voltage is applied.
- 7. Press the label back onto the drive.
- 1. Peel back the Schneider Electric label from the drive, to expose the start point adjustment potentiometer. Refer to Figure-3.
- Start Point Adjustment
- CHECKOUT
- Positioning with Controller
- Go, No Go Test
- 1. Disconnect the field wiring from the red, yellow, and blue leads of the drive.
- 2. Apply power to the actuator.
- 3. Short the yellow and red leads of the drive. The actuator should rotate CW to its limit, unless it is rewired to rotate CCW on an increase in input signal. Disconnect the short between the yellow and red leads.
- 4. Short the yellow and blue leads of the drive. The actuator should rotate CCW to its limit, unless it is rewired to rotate CW on an increase in input signal. Disconnect the short between the yellow and blue leads.
- 5. If the assembled actuator and drive passes steps 3 and 4, they are functioning correctly. If the assembly does not pass these steps, proceed to the next step.
- 6. Unhook the drive leads from actuator terminals x, 2, and 3.
- 7. Short actuator terminals x and two. The actuator should rotate CW to its limit. Disconnect the short. The actuator should stop rotation.
- 8. Short actuator terminals x and three. The actuator should rotate CCW to its limit. Disconnect the short. The actuator should stop rotation.
- 9. If the actuator passes steps 7 and 8, it is functioning correctly. If the actuator does not pass these steps, the drive may still be functional but the actuator must be replaced.
- 1. Disconnect the field wiring from the red, yellow, and blue leads of the drive.
- Manual Positioning
- 1. Apply power to the actuator.
- 2. Disconnect the actuator’s control leads from the controller.
- 3. Attach the leads from the manual positioner (TOOL-202) to the like-colored leads on the drive.
- 4. Manually position the actuator by turning the knob of the manual positioner.
- 5. Check for proper operation of the valve or damper as the actuator is operated.
- 6. Remove power from the actuator.
- 7. Reconnect the actuator wires to the controller.
- 1. Apply power to the actuator.
- MAINTENANCE
Copyright 2010, Schneider Electric
All brand names, trademarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
F-14940-7
www.schneider-electric.com/buildings
Schneider Electric
1354 Clifford Avenue
P.O. Box 2940
Loves Park, IL 61132-2940
On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
cor
p
orate brand chan
g
es.
MAINTENANCE
The drive requires no maintenance.
Regular maintenance of the total system is recommended to assure sustained, optimum
performance.
FIELD REPAIR
None. Replace an inoperative drive with a functional unit.
DIMENSIONAL DATA
4"
(102mm)
1/2" Conduit
Thread
4"
(102mm)
3-1/4"
(83mm)
2-1/2"
(64mm)
1-7/8"
(48mm)
1"
(25mm)
Figure-5 Mounting Dimensions of CP-8301-xxx Series Electronic Actuator Drive.