User Guide
Table Of Contents
- Application
- Features
- Applicable Literature
- . Environmental Controls Cross-Reference Guide, F-23638
- . Environmental Controls Reference Manual, F-21683
- . Environmental Controls Application Manual, F-21335
- . Pneumatic Products Catalog, F-27383
- . MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series Reversible and Proportional Electric Actuators General Instructions, F-15479
- SPECIFICATIONS
- Inputs
- Outputs
- Environment
- Agency Listings
- Table-2 Typical Actuators.
- TYPICAL APPLICATIONS (wiring diagrams)
- INSTALLATION
- WIRING
- ADJUSTMENTS
- Start Point Adjustment
- 1. Peel back the Schneider Electric label from the drive, to expose the start point adjustment potentiometer. Refer to Figure-3.
- 2. Disconnect the red, yellow, and blue leads of the drive from the controller.
- 3. Connect the leads of TOOL-202 to the like-colored leads of the drive.
- 4. Connect a DVM to the yellow (OP1) and blue (COM) leads of the drive.
- 5. Adjust TOOL-202 until the DVM reading equals the required start point voltage (2 to 12 Vdc).
- 6. Adjust the actuator start point, using a small, single-slotted screwdriver, so that the actuator shaft just begins to rotate when the desired voltage is applied.
- 7. Press the label back onto the drive.
- 1. Peel back the Schneider Electric label from the drive, to expose the start point adjustment potentiometer. Refer to Figure-3.
- Start Point Adjustment
- CHECKOUT
- Positioning with Controller
- Go, No Go Test
- 1. Disconnect the field wiring from the red, yellow, and blue leads of the drive.
- 2. Apply power to the actuator.
- 3. Short the yellow and red leads of the drive. The actuator should rotate CW to its limit, unless it is rewired to rotate CCW on an increase in input signal. Disconnect the short between the yellow and red leads.
- 4. Short the yellow and blue leads of the drive. The actuator should rotate CCW to its limit, unless it is rewired to rotate CW on an increase in input signal. Disconnect the short between the yellow and blue leads.
- 5. If the assembled actuator and drive passes steps 3 and 4, they are functioning correctly. If the assembly does not pass these steps, proceed to the next step.
- 6. Unhook the drive leads from actuator terminals x, 2, and 3.
- 7. Short actuator terminals x and two. The actuator should rotate CW to its limit. Disconnect the short. The actuator should stop rotation.
- 8. Short actuator terminals x and three. The actuator should rotate CCW to its limit. Disconnect the short. The actuator should stop rotation.
- 9. If the actuator passes steps 7 and 8, it is functioning correctly. If the actuator does not pass these steps, the drive may still be functional but the actuator must be replaced.
- 1. Disconnect the field wiring from the red, yellow, and blue leads of the drive.
- Manual Positioning
- 1. Apply power to the actuator.
- 2. Disconnect the actuator’s control leads from the controller.
- 3. Attach the leads from the manual positioner (TOOL-202) to the like-colored leads on the drive.
- 4. Manually position the actuator by turning the knob of the manual positioner.
- 5. Check for proper operation of the valve or damper as the actuator is operated.
- 6. Remove power from the actuator.
- 7. Reconnect the actuator wires to the controller.
- 1. Apply power to the actuator.
- MAINTENANCE
F-14940-7 © Copyright 2010 Schneider Electric All Rights Reserved. 3
ACCESSORIES
None
TOOLS
Appropriate screwdriver
TOOL-201 Calibration kit for Schneider Electric System 8000
TM
TYPICAL APPLICATIONS (wiring diagrams)
Refer to Figure-1 for a service application wiring diagram showing the connections between
a CP-8301-xxx series drive and an MP-3xx, MP-4xx or MP-21xx series actuator.
INSTALLATION
Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If
undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
Requirements • Tools (not provided):
– Appropriate screwdriver
– Digital Volt-ohm Meter (DVM)
• Training: Installer must be a qualified, experienced technician
• Other accessories as appropriate
• Wiring diagrams
Blue
CP-8301-XXX
Drive
Yellow
Red
Blue (COM)
Yellow (OP1)
MP-3XX, MP-4XX, MP-21XX
Series Actuator
Typical
Controller
TP-8101
CP-8102
100
Ohm
Slidewire
Wire Nuts
Actuator
Terminals
7
Red (+20)
Brown/White
Brown
Brown/Black
Red/Black
Blue/Black
4
8
3
2
L1 (H)
L2 (G)
Limit
Switches
Field Winding
Power
Yellow/Black
Black
For actuator with internal transformers. Disconnect red and blue
leads from actuator terminals 7 and 8 and tape off.
Diagram shown: increasing input causes CW actuator rotation.
All references to the direction of rotation are determined by looking
at the actuator output shaft.
For CCW rotation with an increasing input signal, reverse the wires
to terminals 7 & 8 and 2 & 3.
x
Part Number Vac Color
CP-8301-120 120 White
CP-8301-240 240 White/Black
CP-8301-024 24 Black/Blue
1
2
3
3
3
3
3
1 2
Shading Windings
Figure-1 Service Application Wiring Diagram.