PRE-INSTALLATION
Inspection
Visually inspect the carton for damage. If damaged, notify the
appropriate carrier immediately. Visually inspect the device
for obvious damage due to shipping. Return damaged parts.
Required Installation Items
Tools (not provided)
Flat blade screwdriver
Small open ended wrench
Two (2) #10 sheet metal screws (provided)
One (1) grommet (provided)
INSTALLATION
See Figure 1. AP-302 Installation.
Caution:
Installer must be a qualified, experienced technician.
Do not locate the device in areas subjected to excessive
vibration or corrosive atmospheres.
1. Cut 5/16" (8 mm) hole in duct.
2. Place grommet over end of probe and slide up probe
until tight against mounting flange.
3. Insert probe and rotate probe until arrow is in direction of
air flow.
4. Mount flange to duct with two (2) #10 sheet metal
screws.
Air Connection Options
1/4" Copper Tubing
1. Install compression fitting to probe air connection.
2. Remove compression nut and copper ferrule from probe
air connection and slide them onto copper tube.
3. Align copper tube to compression fitting and secure.
1/4" Plastic Tubing
1. Install compression fitting to probe.
2. Remove compression nut and copper ferrule from probe
air connection.
3. Slide compression nut onto plastic tube.
4. Discard copper ferrule and slide plastic ferrule onto
plastic tubing.
5. Install tubing insert into end of plastic tubing.
6. Align plastic tubing to compression fitting and secure.
AP-302
Static Pressure Probe
Installation Instructions
Figure-1 AP-302 Installation.