Application
The 2218 Series Pneumatic Room Thermostats are
designed for proportional control of pneumatic valves
and damper actuators in environmental control
systems where a dual presure air main is utilized for
seasonal changeover of heating and cooling functions.
Their design incorporates a highly sensitive, bimetal,
thermostatic element, and a pilot-operated relay with
pneumatic feedback for accuracy and stability over the
entire operating range.
Indexing the thermostat from summer control (reverse
acting) to winter control (direct acting), or vice versa, is
accomplished by remotely changing the main air
pressure supply from 16 psig (summer) to 25 psig
(winter). Models are also available that operate on
slightly different pressures to replace many competitive
devices.
These thermostats have a serrated thumb wheel for
setpoint adjustment. Models are also available with
preassembled internal dial stops. Thermostat covers
are available in various styles to meet particular
requirements. Cover options include models with a
setpoint scale and a thermometer, a setpoint scale
only, a thermometer only, or blank. An external setpoint
adjustment cover is available on some models, or can
be field-installed on covers where desired.
Features
Factory-calibrated, stainless steel ball-in-seat
provides pneumatic feedback for stable, linear
operation.
Snap-acting (not gradual) changeover from direct
action to reverse action operation and vice versa.
Easy-to-use throttling range adjustment and
recalibration.
Adjustable (patented) bimetal shows actual
throttling range in both °F and °C. Adjustable 2 to
12 °F (1 to 6.7 °C).
Leak-proof, self-closing branch gauge tap.
SPECIFICATIONS
Action: Proportional.
Setpoint Range: See Table-1 and Table-2.
Throttling Range: See Table-1 and Table-2.
Supply Air Pressure:
Below 16 psig, Operates at summer setpoint.
Above 25 psig, Operates at winter setpoint.
Maximum Air Pressure: 30 psig.
Main Air Consumption: See Table-1 and Table-2.
Calibration Point: See Table-1 and Table-2.
Summer/Winter Indexing: Remote, by change in main air
pressure.
Setpoint Adjustment: Serrated thumbwheel.
Construction:
Mechanical Components, Die cast aluminum, stainless
steel, and glass-filled nylon.
Diaphragm, Fabric-reinforced Neoprene.
Air Lines, Connect to thermostat nipples with
spring-reinforced plastic tubes.
Branch Connections, Equipped with internal fiters.
Environment
Humidity: 5 to 95% relative humidity, non-condensing.
Locations: NEMA Type 1.
2218 Series
Summer-Winter
Pneumatic Room Thermostats
General Instructions
Full Dial Cover Shown
(Covers must be ordered
separately except as noted.)