User Guide

Printed in U.S.A. 8/06 © Copyright 2006 TAC All Rights Reserved. F-24574-2
TAC
1354 Clifford Avenue
P. O. Box 2940
Loves Park, IL 61132-2940
www.tac.com
Application
The 2211 Series Pneumatic Room Thermostat is
designed for proportional control of pneumatic devices
and actuators in environmental control systems. These
one-pipe thermostats are force-balanced and utilize an
external restrictor in the supply line. Their design
incorporates a highly sensitive bimetal thermostatic
element and a ball valve for pneumatic feedback, which
ensures accuracy and stability over the entire
operating range.
These thermostats have a serrated thumb wheel for
setpoint adjustment. Models are also available with
preassembled internal dial stops. Thermostat covers
are available in various styles to meet particular
requirements. Cover options include models with a
setpoint scale and a thermometer, a setpoint scale
only, a thermometer only, or blank. An external setpoint
adjustment cover is available on some models, or can
be field-installed on covers where desired.
Features
Factory-calibrated, stainless steel ball-in-seat
provides pneumatic feedback for stable, linear
operation.
Easy-to-use throttling range adjustment and
recalibration.
Adjustable (patented) bimetal shows actual
throttling range in both °F and °C. Adjustable 2 to
12 °F (1 to 6.7 °C)
Leak-proof, self-closing branch gauge tap.
SPECIFICATIONS
Action: Proportional.
Setpoint Range: 55 to 85 °F (13 to 29 °C).
Throttling Range: 2 to 12 °F adjustable.
Supply Air Pressure: 20 psig.
Maximum Air Pressure: 30 psig.
Main Air Consumption: 30 scim.
Calibration Point: 9 psig branch line pressure when
ambient equals setpoint.
Setpoint Adjustment: Serrated thumbwheel.
Construction:
Mechanical Components, Die cast aluminum, stainless
steel, and glass-filled nylon.
Diaphragm, Fabric-reinforced Neoprene.
Air Lines, Connect to thermostat nipples with
spring-reinforced plastic tubes.
Branch Connections, Equipped with internal fiters.
Environment
Humidity: 5 to 95% relative humidity, non-condensing.
Locations: NEMA Type 1.
2211 Series
One-Pipe Pneumatic Room Thermostats
General Instructions
Full Dial Cover Shown
(Covers must be ordered
separately except as noted.)