Owner's manual

1
ON
234
Switch #2
OFF = ON/OFF
ON = HI/LOW
See Table Below for
Programming Information
U-GAGE
Q45U Ultrasonic Sensors with Bipolar Discrete Outputs
2 P/N 44177 Rev. D
Banner Engineering Corp. Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
Near and Far Sensing Limit Settings:
The Q45U features a single push button for programming of
sensing window near and far limits (Figure 1). See the
programming procedure on page 4.
Status Indicators:
Status indicator LEDs are visible through the transparent, o-ring
sealed Lexan® top cover. Indicator function in the RUN mode
is, as follows:
The green LED is on steadily whenever power is applied to the
sensor, and flashes to indicate an overloaded output.
The red LED lights when an echo is received, and flashes at a
rate that is proportional to echo strength.
The yellow LED lights whenever the outputs are conducting.
The 5-segment moving dot LED indicator displays the relative
position of the target within the programmed sensing window.
The #1 LED flashes when the target is closer than the near limit.
The #5 LED flashes when the target is beyond the far limit.
Output Response Settings:
IMPORTANT: Remove power before making any internal
adjustments.
Using the two slots shown in Figure 1, a small flat-blade
screwdriver may be used to lift up and remove the black inner
cover to expose the 4-position DIP switch (Figure 2). Those
switches are used to program the following functions:
Limits
N
1 2 3 4 5
Green POWER
Indicator
Red SIGNAL
Indicator
Yellow OUTPUT
Indicator
Push button for
Programming of Sensing
Window Limits
5-Segment Target
Position Indicator
(N = Near)
Slots for Inner
Cover Removal
Figure 1. Q45U Features
Figure 2. Q45U Programming Switches
Switch Function
1
ON/OFF Mode
Output: On = normally closed (output energizes when target is absent)
Off* = normally open (output energizes when target sensed)
2
Mode: On = HIGH/LOW (fill level control, see description, on page 3)
Off* = ON/OFF (output follows sensing action)
3 - 4
Response (20 ms/cycle)
Switch 4
Switch 3
1 Cycle
2 Cycles
8 Cycles*
32 Cycles
Off
On
Off
On
*Denotes factory settings.
NOTE: Response setting of 2 cycles, or higher, is recommended for optimum sonic and electrical noise immunity. Always use the
slowest acceptable response speed for your application. Single cycle update is only recommended for short range
(<50 cm) applications looking for a stationary target (i.e. reflector).
HIGH/LOW Mode
On = Pump Out
Off = Pump In
Off
Off
On
On