User Manual

Switches
Device Settings 1 2 3 4 5 6 7 8
Low resolution (1 degree) ON
Discrete sinking inputs OFF*
Discrete sourcing inputs ON
Thermocouple, J-Type OFF* OFF* OFF* OFF*
Thermocouple, B-Type OFF OFF OFF ON
Thermocouple, C-Type OFF OFF ON OFF
Thermocouple, D-Type OFF OFF ON ON
Thermocouple, E-Type OFF ON OFF OFF
Thermocouple, G-Type OFF ON OFF ON
Thermocouple, K-Type OFF ON ON OFF
Thermocouple, L-Type OFF ON ON ON
Thermocouple, M-Type ON OFF OFF OFF
Thermocouple, N-Type ON OFF OFF ON
Thermocouple, P-Type ON OFF ON OFF
Thermocouple, R-Type ON OFF ON ON
Thermocouple, S-Type ON ON OFF OFF
Thermocouple, T-Type ON ON OFF ON
Thermocouple, U-Type ON ON ON OFF
Modbus or UCT configured (overrides DIP
switches)
ON ON ON ON
* Default configuration
** In high resolution mode, the temperature = (Modbus register value) ÷ 20. In low resolution mode, the temperature = (Modbus register
value) ÷ 2.
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross Wireless I/O Network product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
SureCross DX80 FlexPower Thermocouple Node
P/N 131297 Rev. I www.bannerengineering.com - tel: 763-544-3164 3