Owner's manual

Analog Output Wiring
AOx
GND
dc common
PWR
10-30V dc
sensor
LED Behavior for the Gateways
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. When testing communication
between the Gateway and Node, all radios and antennas should be at least two meters apart or the communications may fail.
LED 1 LED 2 Gateway Status
(solid green)
Power ON
(flashing red) (flashing red)
Device Error
(flashing yellow)
Modbus Communication Active
(flashing red)
Modbus Communication Error
For Gateway and Ethernet Bridge systems, active Modbus communication refers to the communication between the Gateway and the
Ethernet Bridge. For GatewayPro systems, the Modbus communication LEDs refer to the communication internal to the GatewayPro. For
Gateway only systems, the Modbus communication LEDs refer to the communication between the Gateway and its host system (if appli-
cable).
Modbus Register Table
I/O
Modbus Holding Register I/O Type Units I/O Range Holding Register
Representation
Terminal
Block Labels
Gateway or
DX85
Any Node Min. Val-
ue
Max. Val-
ue
Min.
(Dec.)
Max.
(Dec.)
1 1 1 + (Node# × 16) Discrete IN 1 - 0 1 0 1 DI1
2 2 2 + (Node# × 16) Discrete IN 2 - 0 1 0 1 DI2
3 3 3 + (Node# × 16) Discrete IN 3 - 0 1 0 1 DI3
4 4 4 + (Node# × 16) Discrete IN 4 - 0 1 0 1 DI4
5 5 5 + (Node# × 16) Analog IN 1 mA
V
0.0
0.0
20.0
10.0
0 65535 AI1
6 6 6 + (Node# × 16) Analog IN 2 mA
V
0.0
0.0
20.0
10.0
0 65535 AI2
7 7 7 + (Node# × 16) Reserved
8 8 8 + (Node# × 16) Device Message
9 9 9 + (Node# × 16) Discrete OUT 1 - 0 1 0 1 DO1
10 10 10 + (Node# × 16) Discrete OUT 2 - 0 1 0 1 DO2
11 11 11 + (Node# × 16) Discrete OUT 3 - 0 1 0 1 DO3
12 12 12 + (Node# × 16) Discrete OUT 4 - 0 1 0 1 DO4
13 13 13 + (Node# × 16) Analog OUT 1 mA 0.0 20.0 0 65535 AO1
SureCross DX80 Gateway
6 www.bannerengineering.com - tel: 763-544-3164 P/N 134301 Rev. G