Owner manual
6.2.1 Output Types
Type # Description Type # Description Type # Description
Hex Dec Hex Dec Hex Dec
0x80 128 Analog OUT 1 0x60 96 Discrete OUT 1 0x64 100 Discrete OUT NMOS 1
0x81 129 Analog OUT 2 0x61 97 Discrete OUT 2 0x65 101 Discrete OUT NMOS 2
0x82 130 Analog OUT 3 0x62 98 Discrete OUT 3 0x6C 108 Discrete OUT NMOS 3
0x83 131 Analog OUT 4 0x63 99 Discrete OUT 4 0x6D 109 Discrete OUT NMOS 4
0x67 103 Discrete OUT 5
0x6B 107 Switch Power Output 0x68 104 Discrete OUT 6 0x66 102 Multiple Discrete OUT
0x69 105 Discrete OUT 7
0x6A 106 Discrete OUT 8
6.2.2 Units Defined
The units parameter defines the range and/or type of data value associated with an input or output.
Selecting Units from within any configuration tool changes the units definition of several parameters, including threshold,
hysteresis, and delta. For example, if the units are 0-20 mA, the threshold, hysteresis, and delta values are entered as
milliampere values. Selecting Temp C changes the threshold, hysteresis, and delta units to degrees Celsius.
Signed values range from −32768 to +32767 and allow for the measurement of negative values. Signed values are
typically used for measuring temperatures. Signed values are stored as two's complement values.
Unsigned values range from 0 to 65535 and are used to measure values that do not go below zero, such as 4 to 20 mA,
distance, or a counter.
6.2.2 Input Units
Units Description Definition
0 Raw Displays the raw A/D conversion data with data ranges from 0 to 65535. This units type is
typically used only for factory calibration.
LCD: Raw A/D hex value
1 4 to 20 mA Analog unit. Modbus register contents are scaled such that 0 represents 4 mA and 65535
represents 20 mA.
LCD: 4.00mA–20.00mA
2 0 to 20 mA Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and
65535 represents 20 mA.
LCD: 0.00mA–20.00mA
3 Discrete (ON/
OFF)
Default discrete input unit.
LCD: ON/OFF
4 0 to 10V
(Volts)
Analog input using 0 to 10V instead of current. Modbus register contents are scaled such that 0
represents 0V and 65535 represents 10V.
LCD: 0.00V–10.00V
Host Controller Systems